20
Operation
IQ VVC-208 Control
SYSTEM PROGRAMMING (continued)
KEY PRESS
DISPLAY
ACTION
6
Set Temperature Mode
TEMPERATURE
F = FAHRENHEIT or
C = CELSIUS
• Press the LEFT or RIGHT arrow
keys to select the method that
all temperatures will be dis-
played in.
• Press the ”P” key to lock in your
entry
7
Program Setback Time
SETBACK TIME
HH:MM
• Press the numbered prod-
uct keys to select the time in
HH:MM format for activating
Setback mode.
NOTE: 0:00 is default to disable
Setback.
• Press the “P” key to lock in your
entry
8
Program Setback Temperature
SETBACK TEMP
xxx
• Press the numbered product
keys to select the Setback
temperature in the range of
140-300°F.
• Press the “P” key to lock in your
entry
9
Set Hold Time
HOLD TIME
HH:MM
• Type in the length of hold time
required. The value is in the
range of 00:00 to 99:59.
• Press the “P” key to advance to
the next stage or parameter.
10
Set Hold Temperature
HOLD TEMP
xxx
• Type in the desired Hold tem-
perature. Hold Temperature
Range is 140-210°F
• Press the “P” key to advance to
the next stage or parameter.
11
Set Hold Done
HOLD DONE
(AUTOMATIC, MANUAL)
• Press the LEFT or RIGHT arrow
keys to select Hold Done.
• Press the “P” key to advance to
the next stage or parameter.
12
Set Hold Fan Speed
HOLD FAN SPEED
(HIGH, LOW)
• Press the LEFT or RIGHT arrow
keys to select Hold Fan Speed.
• Press the “P” key to advance to
the next stage or parameter.