5.
Communication and Examples
5.1.
Loopback Diagnostic Test
MODBUS
DATA
MODBUS
Addr. Function
CRC-L
CRC-H Telegram: Master ->
Slave
1
8
0
0
AA
55
5E
94
MODBUS
DATA
MODBUS
Addr. Function
CRC-L
CRC-H Telegram: Slave ->
Master
1
8
0
0
AA
55
5E
94
5.2.
Status Check
Interrogate circuit breaker 1 via EB-MODBUS-RTU
MODBUS
DATA
MODBUS
Addr.
Function r/w Start Addr.
Number of
States
CRC
Telegram:
Master -> Slave
Byte
Byte
h-byte l-byte h-byte l-byte l-byte h-byte
1
1
1
245
0
1
150
122
CRC
Number of selected circuit breakers
(devices/register addresses always 1)
Circuit breaker 1, status (register address 501)
See: "Overview of Single Channel Circuit Breaker Functions"
Reading the Outputs
MODBUS RTU Address