6.4.
Coding of the Circuit Breaker Currents
Coding of the tripping currents (registers 401 - 440) is shown in Table 2
Table 4:
Coding of the Tripping Currents
Value
Meaning
500
Tripping current 0.5 A
1000
Tripping current 1 A
2000
Tripping current 2 A
3000
Tripping current 3 A
4000
Tripping current 4 A
5000
Tripping current 5 A
6000
Tripping current 6 A
8000
Tripping current 8 A
10000
Tripping current 10 A
6.5.
EB Variants
Coding of the options (registers 601-640) is shown in Table 2
Table 5:
Coding of the Types
Name
Value
Description
EB-MODBUS-RTU
0xCC10
MODBUS-RTU Communication Module
EB-IO-LINK
0xCC20
IO-
LINK Communication Module
EB-3824-100-0
0xCBAA
Tripping currents can only be set via the interface (0.5
-
10A)
EB-0824-100-0
0xCB8A
Tripping currents adjustable via interface or at the circuit breaker (0.5
-
0A)
EB-1824-010-0
0xCB91
Fixed value 1
A nominal
EB-1824-020-0
0xCB92
Fixed value
2A nominal
EB-1824-030-0
0xCB93
Fixed value
3A nominal
EB-1824-040-0
0xCB94
Fixed value
4A nominal
EB-1824-060-0
0xCB96
Fixed value
6A nominal
EB-1824-080-0
0xCB98
Fixed value
8A nominal
EB-1824-100-0
0xCB9A
Fixed value
10A nominal