The pressure switch is factory fitted during manufacturing process and must not be tampered 
with, disassembled or removed. Any user interference will void warranty. 

Be aware of the danger posed by the protected equipment

When working in the vicinity of 

electrical  equipment  observe  corresponding  safety  rules  and  instructions.  Working  on 
electrical installations may be performed only by qualified persons. 

Install  the  T  Series  so  that  the  pressure  switch  is  not  exposed  to  aggressive  chemical 
substances  (caustic,  acids,  solvents,  corrosive  substances  etc.)  and  in  direct  influence  of 
weather conditions. 

Always place the pressure switch in the lower part of the risk area to avoid direct flames and 
heat.

 

The pressure switch cannot be in direct contact or be in immediate proximity with parts 

which heat to temperatures of more than 80 °C (176 °F). 

 

TxxxES MODELS ONLY 

Parameter 

Description 

Material of body 

nickel plated steel 

Switch point 

set to 1 bar (14 psi) 

Switch configuration 

NO/NC 

Hysteresis 

min. 0.3 bar (4 psi) / max. 1 bar (14 psi) 

Switching frequency 

max. 100 min

-1

 

Maximum pressure 

60 bar (870 psi) 

Power rating 

Angular connector 

All 

Current 

Resistive load AC-12, DC12 

AC 250 V 

DC 24 V 

4 A 

Inductive load AC-14, DC14 

AC 250 V 

DC 24 V 

2 A 

IP rating 

IP65 with cable connector and seal 

Electrical outlet 

DIN EN 175301-803 A 

Operation temperature 

from -20 °C up to 80 °C (-4 °F to 176 °F) 

Tested to 
 
 
 

EN60947 

– Low-voltage switchgear and control gear 

IEC 68-2-78 Permissible air humidity (4K4H per EN 60721-3-4) 
IEC 60068-2-

6 Vibration resistance 10 g (10…….2,000 Hz) 

IEC 60068-2-27 Shock resistance 30 g 

Advantages 

heavy duty, higher power rating, monitoring function, NO/NC  

 
 
 
 
 
 
 

1.

 

Fixing  screw;  use  a  screwdriver  for  installation  and  removal  of  the  connector. 
Tightening torque max. 5 Nm.

 

2.

 

Electrical connector; use flat head screwdriver to remove from the connector body and 
connect the electrical cable.

 

3.

 

Gasket

 

4.

 

Sealing nut to fix the electrical cable. Below the sealing nut is a grommet. Screw the 
sealing nut tight in order to seal the electrical cable properly.

 

 

Cable connector 

 

Pressure Switch models 

TxxxES 

When supplied and before actuation 

(pressurized) 

This is the configuration of the  

Pressure Switch  on models TxxxES 

When actuation has occurred      

(not pressurized) 

This is the configuration of the  

Pressure Switch  on models TxxxES 

Содержание T Series

Страница 1: ...FULLY This user manual contains important information about the BlazeCut T Series fire suppression system its use operation installation and maintenance If further technical information is required please request a copy of the T Series technical manual from a BlazeCut representative ...

Страница 2: ...tely Following skin contact Flush irrigate the affected area with large amount of water Do not use hot water Remove contaminated clothing affected by extinguishing agent If you experience frostbite seek medical attention Following eye contact Carefully flush irrigate with water for several minutes If possible remove contact lenses if they are inserted Continue flushing Seek medical attention Follo...

Страница 3: ...into one unit The BlazeCut T Series is not compatible with other fire suppression systems do not try to connect the system to any other equipment The system may be installed only by adult persons physically and mentally capable Incorrect interference with the system may cause malfunction of the system and provides threat to safety and health of people The system is under constant pressure any mech...

Страница 4: ...18 ft3 0 11 lb 0 07 oz 11 02 in T050E 0 18 m3 0 14 m3 0 10 kg 2 g 53 cm 6 36 ft3 4 94 ft3 0 22 lb 0 07 oz 20 87 in T100E 0 46 m3 0 35 m3 0 25 kg 5 g 113 cm 16 24 ft3 12 36 ft3 0 55 lb 0 17 oz 44 48 in T200E 0 91 m3 0 69 m3 0 50 kg 5 g 215 cm 32 14 ft3 24 37 ft3 1 10 lb 0 17 oz 84 64 in T300E 1 37 m3 1 04 m3 0 75 kg 10 g 319 cm 48 38 ft3 36 73 ft3 1 65 lb 0 35 oz 125 59 in T400E 1 82 m3 1 39 m3 1 0...

Страница 5: ...oisonous unnecessary excessive exposure of persons to its influence should be avoided Under no circumstances should persons be exposed to the extinguishing agent for more than 5 minutes also in case when the extinguishing concentration does not exceed the LOAEL level contact your local BlazeCut supplier for more information During the system activation the extinguishing agent is discharged from th...

Страница 6: ... with the letter S in model designation have an integrated pressure switch that allows connection of signalling devices or to perform a shutdown operation at agent discharge An IP65 Pressure Switch is factory fitted for outdoor and mobile applications T Series models with the letters S E in model designation have an integrated economy pressure switch that allows connection of signalling devices or...

Страница 7: ...ishing effect of the system may be decreased and part or the entire protected enclosure may be damaged 11 Install the system so that it is not exposed to aggressive chemical substances caustic acids solvents corrosive substances etc and avoid direct influence of weather conditions and direct sunlight 12 When fastening the system make sure not to damage other parts of the vehicle or the enclosure 1...

Страница 8: ...100 min 1 Maximum pressure 60 bar 870 psi Power rating Angular connector All Current Resistive load AC 12 DC12 AC 250 V DC 24 V 4 A Inductive load AC 14 DC14 AC 250 V DC 24 V 2 A IP rating IP65 with cable connector and seal Electrical outlet DIN EN 175301 803 A Operation temperature from 20 C up to 80 C 4 F to 176 F Tested to EN60947 Low voltage switchgear and control gear IEC 68 2 78 Permissible ...

Страница 9: ...er pressure in the tube and vice versa IMPORTANT At very low temperatures the pressure of agent vapours is close to zero Indicator on the pressure gauge can vary from 0 bar 0 psi when temperatures are very low to 17 bar 247 psi when temperatures are very high This is not a sign of defect in the system CASES WHEN THE BLAZECUT SYSTEM MUST BE REPLACED The system is leaking was used or emptied from ot...

Страница 10: ... waste NEED SOMETHING MORE If there is a requirement for electronic monitoring external alarm or other size of system these are available Please contact technical blazecutgroup com GLOBAL HEAD OFFICE BlazeCut Pty Ltd 45 Evans St Balmain NSW 2041 Australia Tel 61 2 8006 1300 MANUFACTURER BlazeCut s r o Priemyselná 2521 90027 Bernolákovo Slovakia www blazecut com technical blazecutgroup com BlazeCut...

Отзывы: