precautions to avoid prolonged exposure of extinguishing agent to high temperatures. After use of the system secure the area 
by natural or forced ventilation. Use the system only in permissible ways required by the manufacturer. 

 
BlazeCut Pressure Tube 

Unique BlazeCut Pressure Tube has both storage and detection function which means that the extinguishing agent is stored 
directly in the pressure tube. The pressure tube is made of special heat stabilized plastic resistant to most of alcohols, bases, 
water, ethers, ketones, hydrocarbons, mineral oils, standard fuels, salt solutions, organic acids. 
Always consult use of the system in application with presence of mineral acids, phenol and other aggressive chemicals with 
your supplier. 
Pressure tube is under constant pressure. Do not damage the tube,  do  not  puncture  or  throw.  During transportation secure 
against movement. During transfer do  not rub  against the  ground. Do not mend damaged tube. Do not store or  transport in 
vicinity of strong sources of heat, aggressive chemical substances (caustic, corrosive substances), prevent contact with sharp 
objects, vibrations or loading with other objects. Store in dry and well-ventilated rooms. Protect from sunlight. 
Always handle the pressure tube as if it were under pressure, unless it is directly verified that it is completely empty. 
 

Fittings 

The fittings of the tube close the tube and keep the system under pressure. The fitting is closed by a pressure gauge on one 
end and sealing screw or pressure switch on the other end. The pressure switch is fitted at the factory when ordered. 
Do not try to remove fittings of the tube if it is under pressure. Protect the fittings from corrosive substances during storage and 
transportation. 
 

Pressure Gauge 

Actual pressure in the system can be determined by reading the value on the pressure gauge, which is mounted on the fitting 
tube. Try to install the pressure gauge so that the pressure values can be read. 
 

Pressure Switch 

T Series 

models with the letter “S” in model designation have an integrated pressure switch that allows connection of signalling 

devices or to perform a shutdown operation at agent discharge. An IP65 Pressure Switch is factory fitted for outdoor and mobile 
applications. 
T Series models with the letters 

“S-E” in model designation have an integrated economy pressure switch that allows connection 

of signalling devices or to perform a shutdown operation at agent discharge. An IP54 economy pressure switch is factory fitted 
for indoor and fixed applications only. 
 
Where  there  are  high  risks  of  power  arcing,  BlazeCut  recommends  T  Series  to  be  installed  with  a  pressure  switch  on  all 
applications of 240 V and above, so that the application is immediately deenergized via the use of a T Series pressure switch 
model. 
 
If you have purchased a model with the pressure switch, please refer below in this User Manual or to the T Series Manual for 
more information about the pressure switch and its wiring. 

 

INSTALLATION INSTRUCTIONS 

 

If the BlazeCut T Series system is installed in the engine compartment, the system can be placed either 
on the engine hood or directly into the engine compartment (see figures below). To secure optimal fire 
suppression  effect,  it  is  necessary  to  determine  which  option  is  more  suitable  in  the  given  engine 
compartment. For example, if the engine is under a plastic cover, it is recommended to install the system 
directly into the engine compartment under the plastic cover. 

 

                       Installation on the hood          Installation into the engine compartment 

 

1.

 

The tube in the retail packaging is secured with cable ties. Cut off the cable ties carefully, avoiding damage to the tube. 
Dispose the silicone and plastic protectors used for packing purposes. 

 
2.

 

The  package  contains  high  temperature  cable  ties  for  installation  in  the  protected  enclosure.  It  is  possible  to  use  PVC 
dipped or rubber insulated metal clamps to prevent detachment of the tube in case of a fire. Do not use a steel fastening 
material  for  installation.  If  in  direct  contact,  steel  clamps,  steel  cable  ties  or  wire  will  cause  heat  concentrations  on  the 
pressure tube. This can result in a lower temperature/false actuations. 

Содержание T Series

Страница 1: ...FULLY This user manual contains important information about the BlazeCut T Series fire suppression system its use operation installation and maintenance If further technical information is required please request a copy of the T Series technical manual from a BlazeCut representative ...

Страница 2: ...tely Following skin contact Flush irrigate the affected area with large amount of water Do not use hot water Remove contaminated clothing affected by extinguishing agent If you experience frostbite seek medical attention Following eye contact Carefully flush irrigate with water for several minutes If possible remove contact lenses if they are inserted Continue flushing Seek medical attention Follo...

Страница 3: ...into one unit The BlazeCut T Series is not compatible with other fire suppression systems do not try to connect the system to any other equipment The system may be installed only by adult persons physically and mentally capable Incorrect interference with the system may cause malfunction of the system and provides threat to safety and health of people The system is under constant pressure any mech...

Страница 4: ...18 ft3 0 11 lb 0 07 oz 11 02 in T050E 0 18 m3 0 14 m3 0 10 kg 2 g 53 cm 6 36 ft3 4 94 ft3 0 22 lb 0 07 oz 20 87 in T100E 0 46 m3 0 35 m3 0 25 kg 5 g 113 cm 16 24 ft3 12 36 ft3 0 55 lb 0 17 oz 44 48 in T200E 0 91 m3 0 69 m3 0 50 kg 5 g 215 cm 32 14 ft3 24 37 ft3 1 10 lb 0 17 oz 84 64 in T300E 1 37 m3 1 04 m3 0 75 kg 10 g 319 cm 48 38 ft3 36 73 ft3 1 65 lb 0 35 oz 125 59 in T400E 1 82 m3 1 39 m3 1 0...

Страница 5: ...oisonous unnecessary excessive exposure of persons to its influence should be avoided Under no circumstances should persons be exposed to the extinguishing agent for more than 5 minutes also in case when the extinguishing concentration does not exceed the LOAEL level contact your local BlazeCut supplier for more information During the system activation the extinguishing agent is discharged from th...

Страница 6: ... with the letter S in model designation have an integrated pressure switch that allows connection of signalling devices or to perform a shutdown operation at agent discharge An IP65 Pressure Switch is factory fitted for outdoor and mobile applications T Series models with the letters S E in model designation have an integrated economy pressure switch that allows connection of signalling devices or...

Страница 7: ...ishing effect of the system may be decreased and part or the entire protected enclosure may be damaged 11 Install the system so that it is not exposed to aggressive chemical substances caustic acids solvents corrosive substances etc and avoid direct influence of weather conditions and direct sunlight 12 When fastening the system make sure not to damage other parts of the vehicle or the enclosure 1...

Страница 8: ...100 min 1 Maximum pressure 60 bar 870 psi Power rating Angular connector All Current Resistive load AC 12 DC12 AC 250 V DC 24 V 4 A Inductive load AC 14 DC14 AC 250 V DC 24 V 2 A IP rating IP65 with cable connector and seal Electrical outlet DIN EN 175301 803 A Operation temperature from 20 C up to 80 C 4 F to 176 F Tested to EN60947 Low voltage switchgear and control gear IEC 68 2 78 Permissible ...

Страница 9: ...er pressure in the tube and vice versa IMPORTANT At very low temperatures the pressure of agent vapours is close to zero Indicator on the pressure gauge can vary from 0 bar 0 psi when temperatures are very low to 17 bar 247 psi when temperatures are very high This is not a sign of defect in the system CASES WHEN THE BLAZECUT SYSTEM MUST BE REPLACED The system is leaking was used or emptied from ot...

Страница 10: ... waste NEED SOMETHING MORE If there is a requirement for electronic monitoring external alarm or other size of system these are available Please contact technical blazecutgroup com GLOBAL HEAD OFFICE BlazeCut Pty Ltd 45 Evans St Balmain NSW 2041 Australia Tel 61 2 8006 1300 MANUFACTURER BlazeCut s r o Priemyselná 2521 90027 Bernolákovo Slovakia www blazecut com technical blazecutgroup com BlazeCut...