180-CL2714.SP v1.00
July 30, 2020
Page 22
Clarity CL2714 SP
INSTALLATION PLANNING
The included label plate, shown below, must be permanently attached inside the cavity of the fireplace in a
visible location.
WARNING: This fi replace has been converted for use with a gas fi replace insert
only and cannot be used for burning wood or solid fuels unless all original
parts have been replaced, and the fi replace reapproved by the authority having
jurisdiction.
AVERTISSEMENT: Ce foyer a été converti
pour l’utiliser avec un encastrable au gaz et
ne peut pas être utilisé pour brûler du bois
ou d’autres combustibles solides, à moins
que toutes les pièces d’origine aient été
remplacées et que le foyer ait été approuvé à
nouveau par les autorités compétentes.
170-0166
Minimum fi replace dimensions /
Dimensions minimales du foyer
Minimum fl ue size /
Taille minimale de la cheminée
6” x 6” /
152mm x 152mm
Height / Hauteur
20” / 508 mm
Depth / Profondeur
15 1/2”/ 394 mm
Width (rear) / Largeur (arrière)
22” / 559 mm
Width (front) / Largeur (avant) 29 1/8” / 740 mm
•
Cutting any sheet-metal parts of a steel solid fuel
burning fireplace, in which the gas fireplace insert is
to be installed, is prohibited.
•
The fireplace flue damper can be fully blocked open
or removed for installation of the gas fireplace insert.
•
The fireplace and fireplace chimney must be clean
and in good working order and constructed of non-
combustible materials.
•
Chimney cleanouts must fit properly.
Check local
codes whether
a continuous
length is
required or if
certified joiner
kits may be
used.
Minimum 8 ft. Maximum 36 ft.
Flashing
Co-linear DV vertical
termination cap
Air
Intake
Exhaust
Flue
FACTORY BUILT FIREPLACE OR ZERO CLEARANCE
FIREPLACE
• Ensure that there is a minimum base of sheet metal
below the unit upon installation along with supplied
levelling bolts.
•
If the factory-built fireplace has no gas access
hole(s) provided, an access hole of 1.5” (37.5 mm)
or less may be drilled through the lower sides or
bottom of the firebox in a proper workmanship-like
manner. This access hole must be plugged with non-
combustible insulation after the gas supply line has
been installed.
• Refractory, glass doors, screen rails, screen mesh,
and log grates can be removed from the fireplace
before installing the gas fireplace insert.
•
Smoke shelves, shields, and baffles may be removed
if attached by mechanical fasteners.
•
Trim panels or surrounds shall not seal ventilation
openings in the fireplace.
Massachusetts installations (Warning): This product must be installed by a licensed plumber or gas fitter when
installed within the Commonwealth of Massachusetts. Other Massachusetts code requirements: Flexible
connector must not be longer than 36in., a shut off valve must be installed; only direct vent sealed combustion
products are approved for bedrooms/bathrooms. A carbon monoxide detector is required in all rooms
containing gas fired direct vent appliances. The fireplace damper must be removed or welded in the open
position prior to installation of a fireplace insert.