180-AF25 v1.11 per PE32 revs
March 15, 2021
Page 13
AF25
INSTALLATION INSTRUCTIONS
MINIMUM CLEARANCES for AF25
Minimum clearances to combustibles
Measured from firebox door flange
A
Side of door flange to combustible wall.
13.5" / 343 mm
B
Top of door flange to bottom of mantel and combustible facing.
20" / 508 mm
C
Side of door flange to side of combustible facing.
10" / 254 mm
D
Mantle width maximum.
12" / 305 mm
E
Minimum hearth side extension *
8"*
F
Mimimum hearth front extension
16" USA / 18" CANADA
* Measured from each side of the fuel loading and ash removal openings / mesuré de chaque coté de l’ouverture de la porte
de chargement et du tiroir de cendre