![BLAUBERG KOMFORT EC LB S11 Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/blauberg/komfort-ec-lb-s11/komfort-ec-lb-s11_operation-manual_2769868005.webp)
www.blaubergventilatoren.de
5
KOMFORT EC LB/LBE S11
Parameters
KOMFORT EC
LB300 S11
KOMFORT EC
LBE300-3 S11
KOMFORT EC
LB400 S11
KOMFORT EC
LBE400-3 S11
KOMFORT EC
LB600 S11
KOMFORT EC
LBE600-3 S11
Unit voltage [V /50-60 Hz]
1~230
Fan power [kW]
0,138
0,306
0,34
Fan current [A]
0,9
2,0
2,2
Electric heater power [kW]
-
3,0
-
3,0
-
3,0
Electric heater current [A]
-
13,0
-
13,0
-
13,0
Total unit power [kW]
0,138
3,138
0,306
3,306
0,34
3,34
Total unit current [A]
0,9
13,9
2,0
15,0
2,2
15,2
Max. air capacity [m
3
/h]
300
450
940
RPM
1380
2600
1740
Sound pressure level at 3 m distance [dB(A)]
24-45
28-47
28-47
Transported air temperature [°C]
from -25 to +60
Casing material
aluzinc
Insulation
25 mm mineral wool
Extract filter
cassette type G4
Supply filter
pocket type G4 (F7)*
Connected air duct diameter [mm]
160
200
250
Weight [kg]
40
42
45
47
77
80
Heat recovery efficiency [%]
86 up to 98
85 up to 98
81 up to 98
Heat exchanger type
counter-flow
Heat exchanger material
polystyrene
*option
OPERATING LOGIC
Cold fresh air from outside flows into the unit, where it is cleaned in the
supply filter. Then the air flows through the heat exchanger and is moved to
the room with the supply fan.
Warm extract air from the room flows into the unit and is cleaned in
the extract filter. Then the air is moved through the heat exchanger and is
exhausted outside with the extract fan.
Cold intake air is heated in the heat exchanger by the heat energy of
warm and humid extract air. The air flows are fully separated while flowing
through the heat exchanger.
Heat recovery minimizes heat losses caused as compared to traditional
window ventilation and saves energy.
In summer the heat exchanger performs reverse and transfers a part
of the accumulated coolness from the cooled extract air for warming up
of intake air. This contributes to better performance of the air conditioner
in ventilated premises.
DELIVERY SET
Air handling unit - 1 item;
Operation manual - 1 item;
Wall-mounted control panel − 1 item
Packing box - 1 item.
ATTENTION
Make sure the unit has no visible transport
damages while accepting the goods. Check the ordered and the
delivered goods for compliance.
!
TECHNICAL DATA
Table 1. Technical data
Model
G4 replaceable filter
(pocket type)
F7 replaceable filter
(pocket type)
G4 replaceable filter
(cassette type)
Duct humidity sensor
KOMFORT EC LB300 S11
FPT-EC LB/LBE300 G4
FPT-EC LB/LBE300 F7
FP-EC LB/LBE300 G4
FS1
KOMFORT EC LBE300-3 S11
KOMFORT EC LB400 S11
FPT-EC LB/LBE400 G4
FPT-EC LB/LBE400 F7
FP-EC LB/LBE400 G4
KOMFORT EC LBE400-3 S11
KOMFORT EC LB600 S11
FPT-EC LB/LBE600 G4
FPT-EC LB/LBE600 F7
FP-EC LB/LBE600 G4
KOMFORT EC LBE600-3 S11
Table 2. Accessories
KOMFORT_EC_LBE_v1(3)_EN.indd 5
11.08.2015 9:01:18