KOMFORT EC LB/LBE S11
TECHNICAL MAINTENANCE
Regular technical supervision and maintenance of the unit are required to
ensure the product long service life and non-stop operation.
Disconnect the unit from power supply prior to any maintenance
operations.
WARNING! Consider the unit sharp edges! Fulfil maintenance
operations in work gloves!
The unit must undergo technical maintenance 3 to 4 times a year.
The unit technical maintenance includes regular cleaning and other works:
1. Filter maintenance (3-4 times per year).
Dirty filters increase air resistance in the system and reduce supply air
volume. The filters require cleaning not less than 3-4 times per year. Vacuum
cleaning is allowed. After two consecutive cleanings filters must be replaced.
For new filters contact the Seller.
Dirty filters are not considered as a warranty case!
Replace immediately humid and mouldy filters!
Filter removal is as follows:
1. Unlatch the panel.
2. Open the service panel carefully supporting it with hand.
3. Remove the filters from the unit.
2. Heat exchanger maintenance (once a year).
Some dust may accumulate on the heat exchanger block even in case
of regular maintenance of the filters. To maintain the high heat recovery
efficiency, regular cleaning is required. To clean the heat exchanger pull it out,
flush the heat exchanger with warm detergent solution. After cleaning install
the dry heat exchanger back to the unit.
Heat exchanger removal is as follows:
1. Unlatch the panel.
2. Open the service panel carefully.
3. Remove the heat exchanger from the unit. Support it with hand to avoid
its falling.
3. Fan maintenance (once a year).
Even in case of regular maintenance of the filters, some dust may
accumulate inside the fans and reduce the fan performance and supply air
flow. Clean the fans with a soft brush or cloth. Do not use water, aggressive
solvents or sharp objects as they may damage the impeller.
QF
WARNING
Cut power supply to the unit off by turning the automatic electric switch from ON to OFF position
prior to any maintenance operations. Take steps to prevent activation of the automatic switch before
finishing all the operations.