Controller power supply:
100-250 V, 50 (60) Hz, maximum power consumption – 30 W.
Controller inputs
Input purpose
Input type
Signal type
Designation
Operation
logic
Comments
Outdoor air temperature
Analogue
NTC 10 kOm
T1
-40...+120 °C
Supply air temperature or temperature
downstream of the main air heater
Analogue
NTC 10 kOm
T2
-40...+120 °C
Extract air temperature
Analogue
NTC 10 kOm
T3
-40...+120 °C
Exhaust air temperature
Analogue
NTC 10 kOm
T4
-40...+120 °C
Return heat medium temperature
Analogue
NTC 10 kOm
T5
-40...+120 °C
External set point adjuster
Analogue
0-10 V
10 V IN
Enables fan speed control by means of a potentiometer.
This input is enabled/disabled via the Engineering Menu
(sensors). The terminal is energised with 10 V.
Main humidity sensor
Analogue
0-10 V
RH
Each of the sensors is enabled/disabled via the
Engineering menu. The sensors are energised with
24 V for powering external sensors. The power supply
overload protection is triggered by a short circuit or
a total current on the 24 V line in excess of 700 mA.
Once the overload protection is activated, the power is
restored only after a manual reset at the power supply
unit.
Main VOC sensor
Analogue
0-10 V
VOC
Main CO
2
sensor
Analogue
0-10 V
CO2
Main PM2.5 sensor
Analogue
0-10 V
PM2.5
Constant flow/pressure supply
Analogue
0-10 V
P1/Q1
Constant flow/pressure exhaust
Analogue
0-10 V
P2/Q2
Supply fan control
Digital
Open
collector/
dry contact
M1 (TACHO)
NC
The control feature can be configured to fan tach pulses
or an external dry contact, or disabled. You can also
program the number of tach pulses per fan revolution
and the alarm condition detection time.
Extract fan control
Digital
Open
collector/
dry contact
M2 (TACHO)
NC
Supply filter contamination control
Digital
Dry contact
FILTER (IN SU)
NO
Extract filter contamination control
Digital
Dry contact
FILTER (IN EXH)
NO
Heat medium flow control
Digital
Dry contact
L1
NC
This input is enabled/disabled via the Engineering Menu.
Heat medium pressure control
Digital
~220 V
L2
NC
This input is enabled/disabled via the Engineering Menu.
Fire alarm sensor
Digital
~220 V
L3
NC
This input is enabled/disabled via the Engineering Menu.
Boost switch
Digital
~220 V
L4
NO
This input is enabled/disabled via the Engineering Menu.
Fireplace switch
Digital
~220 V
L5
NO
This input is enabled/disabled via the Engineering Menu.
Electric preheating thermostat (alarm)
Digital
~220 V
NKP TRIAC (IN)
NC
Electric reheater thermostat (alarm) or
water heater capillary thermostat (alarm)
Digital
~220 V
NKD TRIAC (IN)
NC
Controller outputs
Output purpose
Output type Signal type
Designation
Note
Supply fan control
Analogue
0-10 V
M1 (OUT 0-10) You can configure the minimum and the maximum value of the signal sent
to an active fan and the delay before switching to automatic control after
activating the unit.
Extract fan control
Analogue
0-10 V
M2 (OUT 0-10)
Analogue control of the reheater or
water heater valve control
Analogue
0-10 V
0-10V OUT (1) The operation of this output depends on the heater type selected via the
Engineering Menu:
Electric.
The system controls an external circuit board which operates the
heater (e.g. multi-stage)
Water.
2-10 V valve control signal.
Analogue control of the bypass or
analogue control of the rotary heat
exchanger
Analogue
0-10 V
0-10V OUT (2) The operation of this output depends on the unit configuration.
Analogue control of the cooler
Analogue
0-10 V
0-10V OUT (3) The operation of this output depends on the cooler type selected via the
Engineering Menu:
Discrete.
Output inactive.
Analogue.
The output will control the built-in or external cooler with its
own control circuit.
Recirculation control
Analogue
0-10 V
0-10V OUT (4)
Electric preheater control
External TRIAC control
NKP TRIAC (OUT) PWM signal is modulated to an external TRIAC with a 10 second cycle.
Electric reheater control
External TRIAC control
NKP TRIAC (OUT) PWM signal is modulated to an external TRIAC with a 10 second cycle.
Electric preheater release
Relay
3A,
=30 V/~250 V
NKP
Electric heater release or water heater
pump release
Relay
3A,
=30 V/~250 V
NKD
Supply damper actuator control and/or
supply fan frequency converter release
Relay
3A,
=30 V/~250 V
VALVE1
Содержание S21
Страница 1: ...WIRELESS CONTROL SYSTEM User s manual EN S21 ...
Страница 2: ...www blaubergventilatoren de S21 2 ...
Страница 25: ...www blaubergventilatoren de S21 25 ...
Страница 26: ...www blaubergventilatoren de S21 26 ...
Страница 27: ...www blaubergventilatoren de S21 27 ...
Страница 28: ...www blaubergventilatoren de B55 8EN 02 ...