Cooler control mode.

  Two options are available: 

manual (on) 

and 

auto

. If discrete is selected, the cooler can be switched on manually 

or automatically. If analogue is selected, the 0...100 % cooler control slider appears on selecting the manual mode. 

Min. time before OFF. 

 The minimum time for the cooler operation before deactivation. 

Min. time before ON. 

 The minimum time for the cooler idling before re-activation. 

Cooler hysteresis. 

Available for coolers with discrete control. 

Bypass/rotary heat exchanger control mode. 

 Displays the bypass control mode or the rotary heat exchanger control mode depending 

on the unit configuration.  The following modes are available for discrete configurations of the bypass/rotary heat exchanger: 

close/run, 

open/stop, auto.

 The following modes are available for analogue configurations of the bypass/rotary heat exchanger: 

manual

 and 

auto

If manual mode is enabled, the 

0...100 %

 bypass/rotary heat exchanger control slider appears.  The 0 % value corresponds to a completely 

closed position of the bypass or maximum speed of the rotary heat exchanger. 

Freeze protection. 

Types of heat exchanger freeze protection.

Freeze protection is activated if the outdoor temperature drops below -3 °С and the supply and extract fans are enabled. Freeze protection 
is deactivated when the outdoor temperature raises above -1 °С or if the supply or extract fan is disabled. 

Protection by supply fan

The fan speed is smoothly changed to maintain the temperature of +5 °С in the exhaust duct downstream of the heat exchanger. 

Protection by bypass

The protection is activated if the bypass is set to automatic and the air temperature in the exhaust duct downstream of the heat 
exchanger drops below +5 °С (+3 °С for a two-point bypass). Protection is deactivated if the bypass is opened/closed manually or if the 
air temperature in the exhaust air duct downstream of the heat exchanger raises above +7 °С (+6 °С for a two-point bypass). The bypass 
maintains the temperature of +5 °С in the exhaust duct downstream of the heat exchanger.

Note:

 the freeze protection operates only if the main heater is enabled, the bypass is installed on the outdoor side and 

Heating

 or 

Auto

 

mode is selected. 

Protection by electric preheater 

If freeze protection is activated, the preheater maintains the temperature of +5 °С in the exhaust duct downstream of the heat exchanger. 

Note:

 deactivate freeze protection at your own risk. This information is also provided in the corresponding on-screen warning. 

While selecting protection by preheater make sure that the preheater is connected to the unit to avoid triggering an alarm condition and 
causing the unit to shut down.  

Содержание S21

Страница 1: ...WIRELESS CONTROL SYSTEM User s manual EN S21 ...

Страница 2: ...www blaubergventilatoren de S21 2 ...

Страница 3: ...aintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country The information in this user s manual was correct at the time of the document s preparation The Company reserves the right to modify the technical...

Страница 4: ...Vcc 24 V Vcc 24 V Vcc 24 V Vcc 24 V Vcc 24 V Vcc 24 V 0 10 0 10 0 10 0 10 0 10 0 10 GND GND GND GND GND GND GND In GND In GND In GND In GND In In In Out Out Out Out In In L M M1 GND A B 24 V RS 485 M2 FILTER 220 V L1 L2 L3 L4 L5 NKD NKP VALVE1 VALVE2 KKB BPS L N L N GND In L N L N NO NO NO NO NO NO NC C C C C C C L N 0 10V OUT M N L N NTC N L N L N L N L L 220V 50Hz 10kOm NTC 10kOm 10kOm NTC 10kOm...

Страница 5: ...ssure control Digital 220 V L2 NC This input is enabled disabled via the Engineering Menu Fire alarm sensor Digital 220 V L3 NC This input is enabled disabled via the Engineering Menu Boost switch Digital 220 V L4 NO This input is enabled disabled via the Engineering Menu Fireplace switch Digital 220 V L5 NO This input is enabled disabled via the Engineering Menu Electric preheating thermostat ala...

Страница 6: ...nger Two relay outputs 3A 30 V 250 V 3A 30 V 250 V BPS The operation of this output depends on the unit configuration Discrete bypass Opening the bypass closes the BPS relay C NO and opens the BPS relay C NC Closing the bypass opens the BPS relay C NO and closes the BPS relay C NC Rotary heat exchanger Discrete The output will directly control the actuator Analogue The output will be used for actu...

Страница 7: ...access point FAN 16 characters of the ID number indicated on the control board and on the unit casing Wi Fi access point password 11111111 Start the application and create a new connection 1 Enter the application menu 2 Select Connection At Home from the menu 3 If the mobile device is connected to the unit Wi Fi access point directly without a router select the Default connection If connecting via...

Страница 8: ...curity WPA2 PSK password protected The most secure type of data encryption for modern network devices WPA WPA2 PSK password protected recommended Security best combined technology that activates WPA and WPA2 and at the same time provides maximum compatibility with any devices Enter your access point password and press the APPLY button Client operation mode on the home router network Enter the home...

Страница 9: ...e Wi Fi name Setup mode Wi Fi password 11111111 the unit password is ignored Type of the Ethernet IP address DHCP RS 485 address 1 The transmission rate of the RS 485 115200 baud RS 485 stop bits 2 RS 485 parity none Engineering menu password 1111 CLOUD SERVER CONNECTION The units can be controlled using the mobile app via a cloud server connection This function allows controlling the unit that is...

Страница 10: ...c heater or with the outdoor air heat ventilation cooling the unit only cools air by means of the cooler or with the outdoor air cold auto the control system automatically determines if air heating or cooling is necessary correspondingly Filter replacement indicator Red colour alarm indication orange colour warning indication Electric heater cooling indicator preheating or reheating before switchi...

Страница 11: ...emperature units for display Temperature setting for the normal mode when the timer and weekly schedule mode are disabled Operating mode select the operating mode to affect the normal mode timer and the weekly schedule Ventilation no temperature control heat recovery only Heating only air heating with the electric heater or the outdoor air heat Cooling only air cooling by means of the cooler or wi...

Страница 12: ...sage Timers Timer settings are made in the Menu Basic Settings Timers Main timer Timer mode settings When the timer is activated in the Home page menu the unit temporarily goes to the following settings Pre set speed selection 1 2 3 standby Timer setting Select the desired temperature control level The temperature control level can be selected in a 15 C 30 C range or disabled off If off is selecte...

Страница 13: ... as scheduled according to the following parameters Pre set speed selection 1 2 3 standby Time setting for a specific time segment Control temperature selection Options available 15 C 30 C off If OFF is selected temperature control will not be performed for a specific period of time For proper operation of Schedule make sure to set the correct date and time Date and time Go to Menu Basic settings ...

Страница 14: ...sure switches only Total operating time of the unit displays the unit total operating time non resettable CONNECTION RS 485 setup Go to Menu Connection RS 485 setup Default settings Controller address 1 RS 485 baud rate 115200 baud RS 485 stop bits 2 RS 485 parity none Note you can use the RS 485 bus to connect up to 16 units slave devices and up to 16 control panels master devices The slave and m...

Страница 15: ...r technical specialists only Select this IP address type at your own risk Then press the APPLY button If the control system fails to detect an Ethernet adapter the Ethernet adapter not available message is displayed ENGINEERING MENU Entering engineering menu Go to Menu Engineering menu Enter the engineering password By default the password is 1111 To change the engineering password go to Menu Engi...

Страница 16: ...ntrol function for this mode according to setpoint selected only 15 С temperature is maintained provided the unit is equipped with a heater and the Heating or Auto mode is selected in the Basic settings Temperature as well as the air quality management function will not be available If the unit is controlled with an external 0 10 V input or if the PI controller is triggered by a humidity CO2 РМ2 5...

Страница 17: ...k from the outdoor temperature sensor Affects the water heater and cooler operation In the winter season the cooler is disabled while the water heater provides preheating of the circuit before the unit start Main heater type The main heater control mode option becomes available while selecting the electric heater or the water heater Note if the water heater is active prior to disabling it make sur...

Страница 18: ... С and the supply and extract fans are enabled Freeze protection is deactivated when the outdoor temperature raises above 1 С or if the supply or extract fan is disabled Protection by supply fan The fan speed is smoothly changed to maintain the temperature of 5 С in the exhaust duct downstream of the heat exchanger Protection by bypass The protection is activated if the bypass is set to automatic ...

Страница 19: ...reeze protection by supply fan or by bypass with the heater disabled 0 10 V control device If this input is enabled the unit stops responding to pre set speeds 1 2 3 and will respond to an external pot resistor connected to the control circuit board To enable this control option the unit must be in any mode other than Standby Fire alarm sensor Make sure that the fire alarm sensor is connected befo...

Страница 20: ...eck for the latest firmware update connect the unit to a router with Internet access Then press the Check for updates button If your unit is running the latest firmware version the corresponding message is displayed If a newer version is available the screen will show the new firmware version and a complete history of changes and the Upgrade firmware button becomes active Once you press the Upgrad...

Страница 21: ...85 and Ethernet connections Engineering password Go to Menu Engineering menu Engineering password Use this menu to change the engineering password Alarms Go to Menu Engineering menu Alarms This menu displays alarms and warnings Alarms are highlighted in red warnings are highlighted in black Alarm indicates a serious error in operation The unit is forcibly turned off The alarm is reset manually usi...

Страница 22: ...at exchanger freeze protection is active 9 Alarm Short circuit of the extract air temperature sensor Determined if the heat exchanger freeze protection is active 10 Alarm Actuation of the protecting preheater thermostat Determined if the preheater is selected for protecting the heat exchanger from freezing NKP IN 11 Alarm Actuation of the protecting preheater thermostat Determined if electric or w...

Страница 23: ...losing the discreet input FILTER IN EXH 30 Alarm No water pressure detected Determined if no water pressure is detected provided that the water heater and the water pressure sensor are enabled 31 Alarm No water flow detected Determined if no water flow is detected provided that the water heater and the water flow sensor are enabled 32 Alarm Low return water temperature 33 Alarm Supply fan cannot p...

Страница 24: ...ow for Schedule mode Air flow according to the analogue input Humidity СО2 РМ2 5 or VOC threshold increase Air flow PI controller based on worst case parameter Standby mode selected Timer ON Standby ON Boost ON Schedule ON 0 10V input activated Analogue input value 0 Preset speed 1 2 3 or manual speed setting yes yes yes yes yes yes yes no no no no no no no no no yes yes ...

Страница 25: ...www blaubergventilatoren de S21 25 ...

Страница 26: ...www blaubergventilatoren de S21 26 ...

Страница 27: ...www blaubergventilatoren de S21 27 ...

Страница 28: ...www blaubergventilatoren de B55 8EN 02 ...

Отзывы: