KOMFORT EC SKE270-1.5
Function
Button/Button combination
Indication
ATTENTION! The duct temperature sensor may be adjusted from the wall-mounted control panel only when the unit is OFF!
7
Duct temperature sensor set-up.
Enter the duct temperature sensor setup mode to edit the supply air temperature downstream of the heater.
Changeover to the temperature sensor setup mode.
Indication of changeover to
temperature sensor setup mode
Indication of the current duct
temperature sensor set point
press synchronously
and
Duct temperature sensor set point setting from +16 °C up to +30 °C with 2 °C
increment.
-
Show current temperature sensor set point
-
Exit the duct temperature sensor adjustment mode.
-
8
Filter replacement indicator.
After 3000 operating hours the control panel display shows the warning filter cleaning or replacement indicator instead of the operating temperature to
communicate the need of filter cleaning or replacement. Clean or replace the filters and then reset the motor meter.
Filter replacement indicator
-
Press the button on the control panel to turn the unit off and disconnect it from
power supply. Replace the filters as stated in the "Maintenance" section.
-
After the filter replacement connect the unit to power supply and press a
respective button on the wall-mounted control panel or on the remote controller
to start the unit.
or
-
Resetting motor hours
press synchronously
and
-
9
Date and time setting.
Press a respective button on the wall-mounted control panel to turn the unit off.
-
Changeover to the date and time setup mode
press and hold
press
-
Selection of the adjusted set point. The set point blinks during setup.
The date and time set points are displayed as follows:
1. Minutes; 2. Hours; 3. Week day; 4. Date; 5. Month; 6. Year.
when pressed
press
or
-
Setting of the set point
press
or
-
Exit the date and time setup mode
press
-
Table 3. Unit control and parameter setting (continued)
KOMFORT_EC_SKE270_v2(4)_EN.indd 12
07.08.2015 14:25:48