www.blaubergventilatoren.de
hybrid
17
CONDENSATE DRAINAGE
The Hybrid (Max) (E) series units require condensate drainage.
The units are equipped with drain pans and drain pipes (Ø16 mm) to collect and drain the condensate.
1
2
Location of the drain pipe for suspended (1) and wall-mounted (2) units
Remove the plug from the drain pipe. Connect the drain pipe to the sewage system using the U-trap kit (available upon separate order).
The U-trap must be constantly filled with water. The pipe slope downwards must be at least 3°.
Provide free drainage for the condensed water it is accumulated inside the unit that may cause the equipment damage and condensate
outflow to the room.
3
1
2
3
4
min 3°
1 – drain pipe of the unit; 2 – U-trap; 3 – connecting pipe; 4 – sewage system.
The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C!
If the expected ambient air temperatures are below 0 °C, the condensate drainage system must be equipped with heat insulation and
preheating facilities.
The Hybrid (Max) (E) ERV series units do not require condensate drainage as they are equipped with an enthalpy heat exchanger.