CONNECTION TO POWER MAINS
The air-handling unit is rated for connection to single-phase AC 1~230 V/50 Hz power mains.
The unit must be connected to power mains using durable, insulated and heat-resistant conductors (cables, wires). The cross section of
the conductors must correspond to the power input of the unit (see technical data). The actual conductor cross-section selection must
be based on its type, maximum permissible heating, insulation, length and installation method.
The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the
event of overload or short-circuit.
The position of the external automatic circuit breaker must ensure free access for quick power-off of the unit. The trip current must be in
compliance with the consumption current, refer to Technical data.
To access the terminal block, remove the decorative cover (for Hybrid Max (E) (ERV)) and the service panel.
Route the cables to the control unit through the sealed cable glands in the unit.
Complete the electrical connections as shown in the external connections diagram.
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTUR-
ER’S LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED
AND WILL VOID THE WARRANTY.
DO NOT LAY THE CABLE IN CLOSE PROXIMITY TO THE CONTROL PANEL CABLE!
DO NOT COIL THE CABLE FROM THE CONTROL PANEL IN LOOPS WHILE LAYING IT.