4

Connected to the tubing installed on Port 3 of the SPILLSTOP Actuator Valve, the pneumatic-to-electric Pressure Switch is used to 

power a warning light or other electrical device when the primary pump has failed and SPILLSTOP has shut down the pump (Figure 1). 

When SPILLSTOP triggers a pump shutdown, the device connected to the Pressure Switch will be powered on. When the SPILLSTOP 

is put back into operation after a pump shutdown, the device will be powered off.

1.  The Pressure Switch has three blade-type electrical contact points.

a.  Connect the common, usually white wire of the electrical device to the common (COM) blade on the Pressure Switch.
b.  Connect the live, usually black wire of the electrical device to the normally open (N.O.) blade connection.

2. 

Attach the air tube to Port 3 of the Actuator Valve and connect to the Pressure Switch’s barb connection. 

Optional Pressure Switch

Connected to the tubing installed on Port 3 of the Actuator Valve, the pneumatic Whistle will sound an auditory alarm alerting personnel 

that the primary pump has failed and SPILLSTOP has shut down the pump (Figure 1). When SPILLSTOP triggers a pump shutdown, air 

pressure is shifted from Port 2 to Port 3 of the Actuator Valve to pneumatically power the Whistle. The Whistle comes pre-installed from 

the factory if ordered with the SPILLSTOP. When ordered separately, the Whistle Kit (part number 50-98K) includes the Whistle, tube 

tee and 15 feet of 1/4” tubing. To install the Whistle Kit:

1.  Attach the Whistle to the tubing provided and connect to Port 3 of the Actuator Valve. If the SPILLSTOP includes a Pressure 

Switch and/or an additional Shutoff Valve for a backup pump, use the tee provided with the Kit to install the Whistle in the tubing 

connecting those devices to Port 3. The tee can be inserted at any point in the tubing.

IMPORTANT! The length of tube from the tee to the Whistle must be the same as the length of tube from the tee to the 

Pressure Switch and/or the backup pump Shutoff Valve� The Whistle consumes a high volume of compressed air and 

if not installed properly, can prevent the Pressure Switch and/or the backup pump Shutoff Valve from activating�

2.  Test the Whistle before putting the SPILLSTOP into operation:

a.  Connect an air line to the Regulator and adjust the Regulator to a minimum of 40 psi (2.7 bar). If the SPILLSTOP is installed 

with more than two Shutoff Valves, increase pressure to a minimum of 60 psi (4.1 bar).

b.  Activate the SPILLSTOP by pushing the Float up or raise the Float by turning the SPILLSTOP upside down. Air should start 

flowing through the tube connected to Port 3 to sound the Whistle and, if installed, the Pressure Switch should activate.

Optional Whistle

The SPILLSTOP is normally maintenance free; however, a function test should be performed at least every 90 days to ensure proper 

operation. To perform a function test:

1.  Turn off all air supply to the pump and SPILLSTOP.
2. 

Open the Test Port Plug on the SPILLSTOP lid and fill the SPILLSTOP with approximately 2 cups (.47L) of water.

3.  Turn on the air supply to the pump and SPILLSTOP, and adjust the Regulator to a minimum of 40 psi (2.7 bar). 

The pump should not operate�

4.  Turn off all air supply to the pump and replace the Test Port Plug.
5.  Drain the water from the SPILLSTOP into an appropriate container by opening the Drain Valve on the bottom of the SPILLSTOP. A 

tube or hose should be attached to the Drain Valve when draining fluid.

6.  Close the Drain Valve and turn on the air supply to the pump and SPILLSTOP. The pump should operate normally.

Maintenance

The SPILLSTOP must be serviced after every pump shutdown before being put back into operation. To service the SPILLSTOP:

1. 

Disconnect all air supply to the pump and SPILLSTOP. Remove the SPILLSTOP lid and flush internal areas with water or cleaner 

appropriate for the process fluid being pumped.

a.  Connect an air line to the Regulator and disconnect the plastic tube at Port 2 of the Actuator Valve. Adjust the Regulator to a 

minimum of 40 psi (2.7 bar). Air should be flowing from Port 2. 

b.  Activate the SPILLSTOP by pushing the Float up or raise the Float by turning the SPILLSTOP upside down. Air should 

stop

 

flowing from Port 2.

c. 

If air does not stop flowing from Port 2 when the SPILLSTOP is activated, the Actuator Valve may be clogged or damaged and 

should be cleaned or replaced.

2.  Reassemble the SPILLSTOP and reconnect the Shutoff Valve(s). Adjust the Regulator to a minimum of 40 psi (2.7 bar) to restart 

the pump. If the SPILLSTOP is installed with a Whistle and/or more than two Shutoff Valves, increase pressure to a minimum of 60 

psi (4.1 bar).

Service

Содержание SPILLSTOP

Страница 1: ...ment at risk The fully pneumatic SPILLSTOP system prevents the hazardous spill by safely capturing expelled fluid and automatically shutting down the failed pump Optional warning alarm and backup pump switchover further minimize system downtime for maximum productivity Visit www Blacoh com for literature online Installation and Operation Manual ...

Страница 2: ...ifications Installation Information Model No Serial No Installation Date Body Material Lid Float Material Pump Area and Number Purchased From Contact Phone Email Table of Contents Safety Warnings 2 General Safety 2 ATEX Standard 2 Installation Operation Instructions 3 Shutoff Valves 3 Installation 3 Operation 3 Service 4 Maintenance 4 Optional Whistle 4 Optional Pressure Switch 4 Troubleshooting 5...

Страница 3: ...ILLSTOP with incompatible fluids Consult distributor or factory if you are not sure of the compatibility of fluids with SPILLSTOP Static spark can cause an explosion resulting in severe injury or death Ground SPILLSTOP and pumping system when pumping flammable fluids or operating in flammable environments WARNINGS Danger of serious injury or death could occur if these warnings are ignored CAUTIONS...

Страница 4: ...for the connection from the pipe to the Inlet connection port 3 If using an Exhaust Shutoff Valve when there is positive inlet pressure to the pump install the Exhaust Shutoff Valve in the pump exhaust line at the SPILLSTOP Inlet connection port Figures B and D This valve will close whenever the pump is shut down regardless of whether the SPILLSTOP is activated or not 4 Connect 1 4 plastic tubing ...

Страница 5: ...ng the SPILLSTOP into operation a Connect an air line to the Regulator and adjust the Regulator to a minimum of 40 psi 2 7 bar If the SPILLSTOP is installed with more than two Shutoff Valves increase pressure to a minimum of 60 psi 4 1 bar b Activate the SPILLSTOP by pushing the Float up or raise the Float by turning the SPILLSTOP upside down Air should start flowing through the tube connected to ...

Страница 6: ...PILLSTOP by pushing the Float up or raise the Float by turning the SPILLSTOP upside down Air should stop flowing from Port 2 c If air does not stop flowing from Port 2 when the SPILLSTOP is activated the Actuator Valve may be clogged or damaged and should be cleaned or replaced 6 Reassemble the SPILLSTOP and reconnect Shutoff Valve s Adjust the Regulator to a minimum of 40 psi 2 7 bar to restart t...

Страница 7: ...e to pump it is recommended to install an additional Shutoff Valve Compressed Air to Pump Air to open valve normally closed N C Pump Exhaust Air to SPILLSTOP Connect to Pump Exhaust To optional Whistle Switch WHISTLE Option PRESSURE SWITCH Option N C COM N O TUBING CONNECTION PUMP SHUTOFF VALVE PRIMARY PUMP Port 2 normally open no fluid in SPILLSTOP DRAIN VALVE Port 3 normally closed open when flu...

Страница 8: ...ion OUTLET SPILLSTOP FROM SHOP AIR TUBING INLET ACTUATOR VALVE PUMP EXHAUST AIR PRIMARY PUMP DRAIN SILENCER RECLASSIFIER WHISTLE Option Figure A SPILLSTOP Installation Diagram 1 Pump Shutoff Valve PUMP SHUTOFF VALVE COMPRESSED AIR TO PUMP Figure A 1 Pump Shutoff Valve ...

Страница 9: ...CTUATOR VALVE PUMP EXHAUST AIR PRIMARY PUMP DRAIN SILENCER RECLASSIFIER WHISTLE Option Figure B SPILLSTOP Installation Diagram 1 Pump Shutoff Valve 1 Exhaust Shutoff Valve PUMP SHUTOFF VALVE ELEVATED TANK EXHAUST SHUTOFF VALVE COMPRESSED AIR TO PUMP PROCESS FLUID Figure B 1 Pump Shutoff Valve 1 Exhaust Shutoff Valve ...

Страница 10: ...PILLSTOP Installation Diagram 3 Pump Shutoff Valves PUMP SHUTOFF VALVE COMPRESSED AIR TO PUMP PUMP SHUTOFF VALVE PUMP SHUTOFF VALVE BACKUP PUMP ADDITIONAL PUMP TUBING PUMP EXHAUST AIR HOSE TUBING TUBING Single SPILLSTOP protects multiple pumps with 1 shutoff valve per pump On larger pumps multiple valves could cause reduction in flow due to restriction added to pump exhaust Figure C 3 Pump Shutoff...

Страница 11: ...ves 1 Exhaust Shutoff Valve PUMP SHUTOFF VALVE COMPRESSED AIR TO PUMP PUMP SHUTOFF VALVE PUMP SHUTOFF VALVE BACKUP PUMP ADDITIONAL PUMP TUBING PUMP EXHAUST AIR HOSE TUBING EXHAUST SHUTOFF VALVE ELEVATED TANK PROCESS FLUID TUBING Single SPILLSTOP protects multiple pumps with 1 shutoff valve per pump On larger pumps multiple valves could cause reduction in flow due to restriction added to pump exhau...

Страница 12: ...urn Policy Details regarding warranty and return policy are available on Blacoh s website at www Blacoh com PROUDLY MANUFACTURED IN THE USA Blacoh Headquarters 601 Columbia Ave Bldg D Riverside CA 92507 USA 951 342 3100 www Blacoh com Sales Blacoh com ...

Отзывы: