Chapter 4: E2 Controller
EXAMPLE 1: Temperature Alarm Offset
Figure 4-35. Temperature alarm offset.
If the offset for the temperature alarm is set at 5.0° F (default), the high temperature alarm will cancel when the actual
temperature drops to the High Temperature Alarm setpoint (80.0° F) - the Offset (5.0° F)
or,
80.0° F - 5.0° F = 75.0° F
The High Temperature Alarm will cancel at 75° F.
Conversely, the low temperature alarm will cancel when the actual temperature rises to the Low Temperature Alarm setpoint
(60.0° F) + the Offset (5.0° F)
or,
60.0° F + 5.0° F = 65.0° F
The Low Temperature Alarm will clear at 65.0° F.
EXAMPLE 2: Humidity Alarm Offset
Figure 4-36. Humidity alarm screen.
If the offset for the humidity alarm is set at 5% (default), the high humidity alarm will cancel when the actual humidity drops to
the High Humidity Alarm setpoint (70.0%) - the Offset (5.0%)
or,
70.0% - 5.0% = 65.0%
The High Humidity Alarm will cancel at 65%.
Dirty Filter Timer
Figure 4-37. Dirty filter timer.