Chapter 4: E2 Controller
4.9.8 Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet
Table 4-36. Unsigned Values for HTTP, SNMP/Modbus Holding Registers/Analog Values for BACnet.
BMS
Address
Modbus
Address
BACnet
Address
Description
Default
Direction
100
229
1100
BMS keep alive parameter
0
R/W
101
230
1101
BMS low fan speed for CW units
0
R/W
102
231
1102
BMS run fan speed for CW units
0
R/W
103
232
1103
BMS dehum fan speed for CW units
0
R/W
4.9.9 Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet
Table 4-37. Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet.
BMS
Address
Modbus
Address
BACnet
Address
Description
Default
Direction
100
101
1100
BMS value to pause the unit
0
R/W
101
102
1101
BMS value to reset alarms
0
R/W
102
103
1102
Force rotation of units in group manual or BMS 0
0
R/W
103
104
1103
BMS value to switch CW sources
0
R/W
104
105
1104
BMS value to switch dual power primary
0
R/W