Chapter 4: E2 Controller
4.5.3.3 Critical Alarms
Critical alarms will coincide with automatic shutdown of the A/C unit(s) equipment as needed to prevent possible system
damage. The A/C unit(s) equipment will remain shut down until the alarm condition(s) are no longer sensed and the controller
has been reset.
Some examples of critical alarms are:
• No Airflow (Air-Proving Switch)
• Fire/Smoke Detection
• Off by Internal Alarm (Only for grouped systems)
4.5.3.4 Alarm Screen Messages
Table 4-3. Alarm screen messages.
Alarm Release
Description of Alarm Conditiion
High Temperature
Air temperature is above user-defined alarm setpoint.
Low Temperature
Air temperature is below user-defined alarm setpoint.
High Humidity
Humidity is above user-defined alarm setpoint.
Low Humidity
Humidity is below user-defined alarm setpoint.
Sensor Failure
Sensor is disconnected or faulty. (The failed sensor is identified.)
Communication Failure
External and/or internal communication lost (BMS or pLAN).
Condensate Pan Full
Full. Water level in condensate pan is reaching an unsafe level.
Moisture
Water sensed by any combination of a leak detector or condensate pan level switch.
Fan Failure
Upper, middle, and/or lower fan failure.
Change Filter
Filter replacement time interval elapsed; filter needs to be replaced.
Humidifier Alarm
Humidifier fault detected.
No Airflow
Insufficient airflow per air-proving switch.
Smoke/Fire
An alarm condition detected by the smoke detector or firestat.
Optional Temp High Alarm
Temperature is above alarm threshold (user configurable).
Optional Temp Low Alarm
Temperature is below alarm threshold (user configurable).
Power Source A Lost
Power source A not detected.
Power Source B Lost
Power source B not detected.
Water Temp High Alarm
Supply fluid temperature is above alarm threshold (user configurable).
Water Temp Low Alarm
Supply fluid temperature is below alarm threshold (user configurable).
No Flow (Water Temp Sensors)
No chilled water flow detected by temperature sensors (optional).
No Flow (Flow Switch)
Insufficient flow of chilled water detected by flow switch.