724-746-5500 | blackbox.com
Page 102
724-746-5500 | blackbox.com
Chapter 4: E2 Controller
Variable/Value Descriptions
Table 4-30. Variable/Value Descriptions.
Variable
Description
Description for
Value 0
Description for
Value 1
Description for
Value 2
Description for
Value 3
Description for
Value 4
Description for
Value 5
Description for
Value 6
Fan link control
None
Upper & middle
Upper & lower
Middle & lower
All
—
—
[X] fan speed
control
Manual
Temperature
proportionate
Variance from
average
—
—
—
—
Type of unit
Not selected
CW-12"
CW-24"
AR-12"
AR-24"
W/G-12"
W/G-24"
4.9.3 Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet
Table 4-31. Boolean Values for HTTP, SNMP/Modbus Coils/Binary Values for BACnet.
BMS
Address
Modbus
Address
BACnet
Address
Description
Default
Direction
1
002
1
Global alarm output
0
R
r
003
2
System on status
0
R
3
004
3
Airflow has been proven
0
R
4
005
4
Call for cooling
0
R
5
006
5
Call for humidification
0
R
6
007
6
Call for dehumidification
0
R
100
101
100
BMS value to pause the unit
0
R/W
101
102
101
BMS value to reset alarms
0
R/W
102
103
102
Force rotation of units in group manual or BMS
0
R/W
103
104
103
BMS value to switch CW sources
0
R/W
104
105
104
BMS value to switch dual power primary
0
R/W
105
106
105
BMS value to activate lockout function
0
R/W
106
107
106
Reset dirty filter alarm
0
R/W