ST-130-2 

 

 

2 Functions

The OLC-D1-S can monitor either the 
minimum or the maximum oil level, 
depending on its mounting position and 
incorporation into the safety chain. If the 
minimum and the maximum oil level 
should be monitored, two OLC-D1-S 
devices must be installed. 

2.1  Monitoring of the minimum level 

Lock out 

The compressor is shut off, if the prism 
sticks out of the oil longer than the delay 
time specified by the circuit. 

The OLC-D1-S then opens the output 
contact and the circuit locks out 
electronically: The control voltage to the 
compressor contactor is interrupted. The 
red LED at the face side of the 
opto-electronic unit lights up (figure 1) as 
well as the signal lamp H4. 

 

Reset 

The circuit can be manually reset by 
pressing the reset button. This reset 
button (S4) has to be mounted into the 
switch board. (Connection see 
schematic wiring diagram.) 

機能

 

OLC-D1-S

は取付け位置と安全回路への

組込み方次第で、最小

/

最大いずれのオイ

ルレベルもモニターできます。最小

/

最大

両方のオイルレベルをモニターする場
合には、

2

台の

OLC-D1-S

装置が必要と

なります。

 

2.1 

最小レベルのモニター

 

ロックアウト

 

プリズムユニットがオイルから出た状
態がプリセットされたディレイタイム
を超えて続くと、コンプレッサーは
シャットオフされます。

 

OLC-D1-S

の出力接点が開き、回路は電

子的にロックアウトされます。コンプ
レッサーのコンタクターへの制御電圧
が遮断され、光学式ユニット前面の赤い

LED

(図

1

)と警告ランプ

H4

が点灯し

ます。

 

 

リセット

 

回路は、リセットボタンを押して手動で
リセットできます。リセットボタン(

S4

はスイッチボードに取り付けます(接続
方法は配線図を参照)。

 

 

Abb. 1 Abmessungen und Aufbau

1 Prisma-Einheit
2 Glas-Kegel
3 Dichtung
4 Opto-elektronische Einheit "OLC-D1"

(360° drehbar)

5 Anschlusskabel
6 Schraubkappe

 

1 Prism 

unit 

2 Glass 

cone 

3 Gasket 
4  Opto-electronic unit "OLC-D1" 

(360° revolving) 

5 Connecting 

cable 

6 Screwing 

cap 

Fig. 1    Dimensions and design 

プリズムユニット

 

ガラスコーン

 

ガスケット

 

光学式ユニット「

OLC-D1

 

(360°

回転

接続ケーブル

 

スクリューキャップ

 

寸法と構造

 

Содержание OLC-D1-S

Страница 1: ...ntactless monitoring of the oil level by means of infrared light Depending on the mounting position and electrical connection the same device can be used for monitoring the minimum and maximum oil lev...

Страница 2: ...lly The control voltage to the compressor contactor is interrupted The red LED at the face side of the opto electronic unit lights up figure 1 as well as the signal lamp H4 Reset The circuit can be ma...

Страница 3: ...lektronische Einheit wird als OLC D1 ausgeliefert siehe Seite 2 Abbildung 1 Position 4 andere Spannungen auf Anfrage auch mit UL Abnahme erh ltlich Kabel sind farbkodiert 5 x AWG 20 0 75 mm2 L 2 m HFK...

Страница 4: ...tch board Alternatively the OLC D1 S can also be used in combination with the optional protection device SE C1 for schematic wiring diagram please refer to next page 3 OLC D1 S SH 170 S4 OLC D1 S SE C...

Страница 5: ...lectronical oil level monitoring SE E1 Compressor protection device standard SE C1 compressor protection device with extended functions option Maximum oil level monitoring To monitor the maximum oil l...

Страница 6: ...In the standard scope of delivery this position is sealed with a plug Monitoring of the maximum oil level Mounting position See position 4 in figure 2 This is the position of the sight glass in the s...

Страница 7: ...s l l nger als eine halbe Stunde der Atmos ph re ausgesetzt war die gleiche Menge neuen ls der selben lsorte einf llen 4 1 Mounting the prism unit Mount the OLC D1 S best before the compressor is inst...

Страница 8: ...erstellen dass der Kabelanschluss immer nach unten weist Das OLC D1 S verriegelt wenn die opto elektronische Einheit nicht montiert ist 4 2 Mounting the opto electronic unit Slide the opto electronic...

Страница 9: ...f monitoring device for maximum level Unscrew cap of opto electronic unit and remove opto electronic unit screwing cap see figure 1 The oil level is dispalyed behind the glass cone of the prism unit T...

Страница 10: ...10 ST 130 2 Notes...

Страница 11: ...ST 130 2 11 Notes...

Страница 12: ...560 0082 1 4 2 14F TEL 06 6873 8555 FAX 06 6873 8556 www bitzer jp info bitzer jp Subject to change nderungen vorbehalten 80311102 01 2011...

Отзывы: