SB-600-2
22
3
Application ranges
Permitted refrigerants
R717 (NH
3
)
Oil charge
Polyalphaolefin (PAO)
Hydrocracked mineral
oil
Please refer to the
Technical Information
ST-500 to know which
oils are authorized
Maximum allowable
pressure (PS)
Discharge side: 24 bar
Suction side: 19 bar
Tab. 2: Application ranges
Please refer to the compressor brochures SP-510 and
SP-520 for the application limits.
3.1
Classification of the ACP and of its
components according to the EU directives
The ACP is intended for incorporation into machines in
accordance with the 2006/42/EC Machinery Directive.
The electrical components comply with the EU Low
Voltage Directive 2014/35/EU. Moreover, the pressur-
ized components must comply with the EU Pressure
Equipment Directive 2014/68/EU (PED), except for the
compressors (see below). The Declarations of Con-
formity and the Declarations of the Manufacturers are
available.
ACPs are no "functional wholes" as described in the
PED and are therefore not concerned by the applica-
tion range of the "assemblies" (2014/68/EU Art. 2, 6).
The directive applies therefore only to the individual
pressurized components. The same thing applies to the
CE marking.
Assessment by a notified body: Bureau Veritas, Paris –
"Technical Appraisal" for ASERCOM members PED-
TA_ASE_001_01-DEU
Compressors are excluded from the scope of the PED
(2014/68/EU Article 1 (2) j). This exception is confirmed
by the evaluation of a notified body. Please refer to "Ex-
planations about the Product conformity" AP-100 for
further explanations. Please refer to AP-100 for the
classification of pressurized accessories for com-
pressors.