KT-102-1
13
• Select IQ MODULE CM-RC-01.
• Click the C
ONNECT
button.
• Enter Bluetooth password. Factory setting from firm-
ware version 2.6.58.00 on: "8670", previous ver-
sions: "2"
The C
ONFIGURATION
menu appears with the M
AIN
S
ETUP
window. The compressor module is now connected to
the mobile device.
9.2
Configuring CM-RC-01 with the BEST
SOFTWARE
In its state of delivery, the compressor control module
CM-RC-01 is configured for use with the compressor in
question.
Check all settings in the C
ONFIGURATION
menu and
change them, if necessary. Check in particular the fol-
lowing entries:
• M
OTOR
START
FUNCTION
because of time relay control
of the motor contactors, see chapter Motor connec-
tion, page 9.
• R
EFRIGERANT
. Select "None" (in future select "R744").
• D
ATE
• T
IME
9.3
Capacity control CRII with the BEST SOFTWARE
In the C
ONFIGURATION
menu, further parameters must be
set in the C
ONTROL
FUNCTIONS
SUBMENU
page 13):
• N
UMBER
OF
CAPACITY
REGULATORS
(max. 2).
• Setting the
MINIMUM
/
MAXIMUM
CAPACITY
LIMIT
from BEST
2.8.229.0 SP2 with firmware version 2.3.242.00. The
released compressor range is fixed as standard.
However, the minimum capacity limit can be in-
creased and the maximum capacity limit reduced.
Fig. 13: Configuration of CRII in the BEST SOFTWARE
Содержание 4CTEU-30LK
Страница 26: ...Notes...
Страница 27: ...Notes...