Application limits in part-load operation

Information
Observe information on discharge gas pressure
and operating temperatures and lubrication con-
ditions as specified in KB-130!

The application of the mechanical capacity control is
limited mainly by thermal limits of the lubricants used.
These thermal limits are monitored in dynamic and sta-
tionary operating states by the compressor module and
the defined control algorithms.

The limits of the discharge gas temperature are:

• Warning: 140°C

• Fault / Switch-off 150°C

• Reset / Unlock 135°C

6FTEU-35LK to 6CTEU-50LK, 33%

10

60

50

40

30

20

20

140

120

100

80

60

40

p [bar]

h

p [bar]

o

t

= 10 K

oh

t [°C]

o

20

15

10

5

0

-10

-20

-30

Motor 1

Motor 2

Fig. 9: Application limit 6FTEU-35LK to 6CTEU-50LK, 33%

t

o

Evaporation temperature (°C)

Δt

oh

Suction gas superheat (K)

p

o

Suction pressure abs. (bar)

p

h

High pressure abs. (bar)

IQ range: independent monitoring of the
application limit by the compressor mod-
ule as a function of the discharge gas
temperature.

Tab. 4: Legend application limit

For the part-load application limits of all compressors
with CRII capacity control, see BITZER SOFTWARE
and upon request.

8

Operating the CRII capacity control with the system
controller

8.1

Control via analogue signal

The compressor capacity is regulated via a DC voltage
signal. This type of control is mainly suitable for sys-
tems with simple controllers which are equipped with
an output for 0 to 10 V and a relay, and if the terminal
strip CN14 is used for the BEST SOFTWARE.

• Connection to terminal strip CN13, terminals 1 and

2.

• Control signal: 0 to 10 V direct current voltage for an

analogue output of the system controller

• Control accuracy: ±0.5% at 100%

• Linear control characteristic, see figure.

CRII

0

2

4

6

8

10

12

U [V]

0 .. 10 V

100%

CR

min

CR

min

1

80%

60%

40%

20%

0%

0,2

*

Fig. 10: Control characteristic

• CR

min

:

– 4-cylinder compressors: Starting with 100%, the

compressor capacity can be reduced to 25% (in
future to 10%) if each cylinder head is equipped
with CRII capacity regulators.

– 6-cylinder compressors: Starting with 100%, the

compressor capacity can be reduced to 33% if 2
cylinder heads are equipped with CRII capacity
regulators.

Information
From firmware- version 2.3.242.00, the min-
imum/maximum capacity control step can be
freely set in the BEST SOFTWARE (BEST
2.8.229.0 SP2) (see chapter Capacity control
CRII with the BEST SOFTWARE, page 13).

Содержание 4CTEU-30LK

Страница 1: ...ion of the original document English 2 CRII System Leistungsregelung f r Hubkolbenverdichter f r transkritische CO2 Anwendungen Originaldokument Deutsch 14 4PTEU 6LK 4KTEU 10LK 4JTEU 10LK 4CTEU 30LK 6...

Страница 2: ...cepts and activation of the solenoid valves 8 6 Electrical connection 9 6 1 Motor connection 9 6 2 High pressure switch 9 6 3 Connecting operation monitoring via the BEST SOFTWARE 9 6 4 Schematic wiri...

Страница 3: ...n addition to this Tech nical Information Always keep the operating instructions and this tech nical information in the vicinity of the refrigeration sys tem during the whole lifetime of the compresso...

Страница 4: ...CN7 to CN12 not even for test purposes The voltage applied to the terminals of CN13 must not exceed 10 V The voltage applied to terminal 3 of CN14 must not exceed 24 V Do no apply voltage to the other...

Страница 5: ...TF 2 HP 726 CRII 2 16 CRII 1 24 Fig 2 Dimensional drawing 4JTEU 10LK 4FTEU 20LK Legend see table 1 page 6 403 183 367 336 431 351 142 385 553 653 60 18 256 300 22 M10x1 5 21 DL SL 1 2 14 NPTF 1 4 18 N...

Страница 6: ...mperature sensor HP 3 Low pressure connection LP 6 Oil drain 9 Connection for oil and gas equalisation parallel operation 10 Connection for oil heating 11 Oil pressure connection 12 Oil pressure conne...

Страница 7: ...suc tion side gas flow to the individual cylinder banks is blocked by means of a control piston Full load operation In full load operation the compressor delivers on all cyl inders The magnetic coil s...

Страница 8: ...pacity regulator de energized Capacity regulator constantly activated Capacity regulator activated intermittently cycle time depending on load condition 6 cylinder compressors CRII 1 CRII 2 100 66 33...

Страница 9: ...is not neces sary depending on local regulations The compressor module is provided with an automatic low pressure cut out function 6 3 Connecting operation monitoring via the BEST SOFTWARE The BEST SO...

Страница 10: ...l GND 2 1 3 4 1 2 1 N 1 N 1 N 3 N 5 N 7 N CM RC 01 4 3 2 1 8 7 6 5 13 12 11 10 9 14 15 16 17 18 19 20 21 22 S2 F2 L1 L2 L3 PE F1 Q1 1 0 M 3 F17 230V T1 F3 4A T PE S1 01 F13 2 B1 H3 M1 Y3 2 grey grau b...

Страница 11: ...ith CRII capacity control see BITZER SOFTWARE and upon request 8 Operating the CRII capacity control with the system controller 8 1 Control via analogue signal The compressor capacity is regulated via...

Страница 12: ...tooth interface or USB port with BEST SOFTWARE installed The BEST SOFTWARE can be downloaded for free from the BITZER website www bitzer de For communication via the USB port Plug the BEST interface c...

Страница 13: ...f necessary Check in particular the fol lowing entries MOTOR START FUNCTION because of time relay control of the motor contactors see chapter Motor connec tion page 9 REFRIGERANT Select None in future...

Страница 14: ...19 5 2 Regelkonzepte und Ansteuerung der Magnetventile 20 6 Elektrischer Anschluss 21 6 1 Motoranschluss 21 6 2 Hochdruckschalter 21 6 3 Betriebs berwachung mit der BEST SOFTWARE anschlie en 21 6 4 Pr...

Страница 15: ...ng und diese Technische Information w hrend der gesamten Verdichterlebensdauer an der K lteanlage verf gbar halten 2 1 Autorisiertes Fachpersonal S mtliche Arbeiten an Verdichtern K lteanlagen und der...

Страница 16: ...annung anlegen auch nicht zum Pr fen An die Klemmen von CN13 maximal 10 V anle gen An die Klemme 3 von CN14 maximal 24 V an die anderen Klemmen keine Spannung anlegen An Spannungsausg nge niemals Span...

Страница 17: ...TF 2 HP 726 CRII 2 16 CRII 1 24 Abb 2 Ma zeichnung 4JTEU 10LK 4FTEU 20LK Legende siehe Tabelle 1 Seite 18 403 183 367 336 431 351 142 385 553 653 60 18 256 300 22 M10x1 5 21 DL SL 1 2 14 NPTF 1 4 18 N...

Страница 18: ...hluss f r Druckgastemperaturf hler HP 3 Niederdruckanschluss LP 6 lablass 9 Anschluss f r l und Gasausgleich Par allelbetrieb 10 Anschluss f r lheizung 11 ldruckanschluss 12 ldruckanschluss 16 l berwa...

Страница 19: ...s zu einzelnen Zylinderb nken durch einen Steuerkolben unterbunden Volllastbetrieb Im Volllastbetrieb f rdert der Verdichter auf allen Zylin dern Die Magnetspule siehe Abbildung 6 Seite 19 ist stromlo...

Страница 20: ...ngsregler stromlos Leistungsregler konstant angesteuert Leistungsregler taktend angesteuert Taktdauer ab h ngig vom Lastzustand 6 Zylinderverdichter CRII 1 CRII 2 100 66 33 Leistungsregler stromlos Le...

Страница 21: ...e nach rtli chen Vorschriften nicht notwendig Das Verdichtermo dul ist mit einer automatischen Niederdruckabschalt funktion ausgestattet 6 3 Betriebs berwachung mit der BEST SOFTWARE anschlie en Die B...

Страница 22: ...gnal GND 2 1 3 4 1 2 1 N 1 N 1 N 3 N 5 N 7 N CM RC 01 4 3 2 1 8 7 6 5 13 12 11 10 9 14 15 16 17 18 19 20 21 22 S2 F2 L1 L2 L3 PE F1 Q1 1 0 M 3 F17 230V T1 F3 4A T PE S1 01 F13 2 B1 H3 M1 Y3 2 grey gra...

Страница 23: ...ehe BITZER SOFTWARE und auf An frage 8 Leistungsregelung CRII mit Anlagenregler bedienen 8 1 Steuerung ber Analogsignal Die Verdichterleistung wird ber ein Gleichspannungs signal gesteuert Diese Art d...

Страница 24: ...USB Anschluss mit installierter BEST SOFTWARE Die BEST SOFTWARE kann kostenlos von der BITZER Internetseite www bitzer de heruntergela den werden Bei Kommunikation ber den USB Anschluss BEST Schnitts...

Страница 25: ...n MOTORANLAUF FUNKTION wegen der Zeitrelaissteuerung der Motorsch tze siehe Kapitel Motoranschluss Seite 21 K LTEMITTEL None ausw hlen zuk nftig R744 ausw hlen DATUM ZEIT 9 3 Leistungsregelung CRII mi...

Страница 26: ...Notes...

Страница 27: ...Notes...

Страница 28: ...ra e 15 71065 Sindelfingen Germany Tel 49 0 70 31 932 0 Fax 49 0 70 31 932 147 bitzer bitzer de www bitzer de nderungen vorbehalten Subject to change nderungen vorbehalten80300801 01 2018 80300801 01...

Отзывы: