Modbus Interface manual
LMC341 DIWE
Page 15
7.5. Control
Parameters used to view and control operation of the LMC341 DIWE controller.
Name
Possible
Values
Default
Description
Register
type
Address
Mode
Unit None
Scale 1
uint8
0
Overall unit mode
(Control.PM_Mode)
0: Off
1: On
2: Manual
Holding register
1632
Control Mode
Unit Boolean
Scale 1
uint8
0
Temperature control mode
(Control.CapMode)
0: Suction pressure
1: Room temp control mode
Holding register
1633
Runtime Hours
Unit None
Scale 1
uint16
-
Runtime in hours, wrap around after 7.5 years
(Control.RuntimeHours)
Input register
1634
MBExtOnOff
Unit Boolean
Scale 1
uint8
0
Same function as Input.ExtOnOff, but for Modbus
(Control.MBExtOnOff)
0: Unit Stopped
1: Unit Released
Holding register
1635
TC Setpoint
Unit °C
Scale 100
sint16
-
Condenser TC setpoint
Only used if ambient compensation = Off
(Condens.TC_set)
000 °C - 8500 °C
Holding register
1636
Fan Mode
Unit Boolean
Scale 1
uint8
0
Fan control mode
(Condens.Economy)
0: Eco
1: LowSound
Holding register
1637
Ambient
Comp.
Unit Boolean
Scale 1
uint8
1
Use ambient compensation or fixed condenser
setpoint
(Condens.AmbComp)
0: Off
1: On
Holding register
1638
Setpoint
Unit °C
Scale 100
sint16
-
Capacity controller setpoint
Range depends on compressor and refrigerant
(Capacity.Tset)
-4500 °C - 3500 °C
Holding register
1639
2nd Setpoint
Unit °C
Scale 100
sint16
-
Secondary setpoint
Activated by a digital input
Range depends on compressor and refrigerant
(Capacity.2ndTset)
-4500 °C - 3500 °C
Holding register
1640
Act. Setpoint
Unit °C
Scale 100
sint16
-
Actual setpoint (read only)
(Capacity.ActTset)
-4500 °C - 3500 °C
Holding register
1641
Cap. Request
Unit %
Scale 100
sint16
-
Capacity request
Calculated capacity request
(Capacity.CapReq)
0 - 10000 %
Input register
1642
Cap. Actual
Unit %
Scale 100
sint16
-
Actual capacity
Actual capacity request – limiters might have reduced
the requested capacity
(Capacity.CapAct)
0 - 10000 %
Input register
1643
FI frequency
Unit Hz
Scale 100
sint16
-
Actual FI frequency in Hz
(Capacity.FrqAct)
0 - 10000 Hz
Input register
1644
Cpr. Running
Unit Boolean
Scale 1
uint8
-
Future use
Input register
1645