Page 10
7. Functions
For all registers apply that a more specific description of
the parameters are to be found in the User manual for the
LMC341 DIWE.
The parameter names in brackets are the complete
parameter name as listed in LMT or BEST.
7.1. Status information
This section contains status information parameters.
Many are directly visible on the main menu of the LUP200
display (option).
Name
Possible
Values
Default
Description
Register
type
Address
2ndSetp
Unit None
Scale 1
unit8
0
2nd Setpoint is active
(Animation.2ndSetp)
0: Off
1: Active
Input register
1537
LowSound
Unit None
Scale 1
unit8
0
LowSound fan mode is active
(Animation.LowSound)
0: Off
1: Active
Input register
1538
WinterStart
Unit None
Scale 1
unit8
0
WinterStart is enabled
(Animation.WinterStart)
0: Off
1: Enabled
Input register
1539
HeatRecover
Unit None
Scale 1
unit8
0
Heat recovery is enabled
(Animation.HeatRecover)
0: Off
1: Enabled
Input register
1540
SetPointSrc
Unit None
Scale 1
unit8
0
What setpoint is used right now
(Animation.SetPointSrc)
0: User setpoint
1: 2nd Setpoint
2: Week program
Input register
1541
StatusIcon
Unit None
Scale 1
unit8
0
Unit status - as on the displays main menu
(Animation.StatusIcon)
0: Normal
1: Min run
2: Min pause
3: Oil return
4: Stopped
5: Li m Tc
6: Lim Tdis
7: Lim Tfc
8: Lim dp
9: Lim Psuc
10: Lim Ifc
11: Off
12: Manual
13: Restarting
14: FC Emergency
15: Psuc Emergency
16: Critical Stop
Input register
1542
MinRun
Unit None
Scale 1
unit8
0
Min. compressor run time is active
(Animation.MinRun)
0: Off
1: Active
Input register
1543
MinPause
Unit None
Scale 1
unit8
0
Min. compressor pause is active
(Animation.MinPause)
0: Off
1: Active
Input register
1544
LimTc
Unit None
Scale 1
unit8
0
TC limiter is active
(Animation.LimTc)
0: Off
1: Active
Input register
1545