background image

Symptom

Possible cause

Remedy

The red LED flashes 8 times after
initialisation

- The detection field was not empty during initialisation
- The bearing clamps are not mounted correctly in the profile
- The bearing clamps are set to different angles on the same sensor
- Reflecting background or metal grating

- Carry out the initialisation again
- Click the bearing clamps into the profile correctly
- Set the bearing clamps to the same angle
- Select a different background

The red LED flashes continuously

- Faulty ribbon cable

- Replace the ribbon cable

The red LED flashes twice

- Dark or reflecting ground
- Object in the detection field (no fault)

- Set parameter 7 to «dark / reflecting» 

The door does not open or close 
although nothing has been detected

- The test input has not been activated or an incorrect version has been

activated

- Make sure that the test input has been activated
- Set the correct relay output in accordance with the door

controller (see page 3, test input))

Master initialisation does not work, the
red LED flashes 4 times

- Use of AC voltage

- Convert the sensors to a DC supply

Not all sensors react when carrying out
the master initialisation

- Use of AC voltage
- Connection interrupted along the ribbon cable

- Convert the sensors to a DC supply
- Insert the ribbon cable correctly or replace it

No reaction from the doors, although
detection is taking place

- Initialisation has been carried out on a sensor that is not directly 

connected to the door controller or to the Y adapter

- Carry out initialisation on the sensor that is directly 

connected to the door controller

The sensor functions without the cover
but not with it

- The angle of the bearing clamps has changed
- The cover is of poor quality (has coarse grooves)
- Sensitivity too low

- Check the angle of the bearing clamps
- Replace the cover
- Increase the sensitivity

The red LED flashes 4, 5, 6 or 7 times

- Use of AC voltage
- Configuration error (sensors have been swapped following master

initialisation)

- Sensors have been incorrectly initialised or not initialised at all
- Self-test failed, triggered unexpectedly

- Convert the sensors to a DC supply
- Carry out the initialisation again
- Carry out initialisation on the master (sensor on the door

controller)

- Carry out the initialisation again

Both LEDS (red and green) are lit
permanently

- Supply voltage is not stable enough
- Supply voltage is too low
- Voltage break

- Isolate the sensor from the supply
- Check the power supply
- Switch the supply on again

Detection sometimes takes place whilst
the door panels are moving

- If the floor is very uneven and the door moves, this may lead to 

detection

- Incorrect background parameters have been selected

- Reduce the sensitivity
- Select the correct background parameters
- Set a different angle (ensure safety requirements are met)

Incomprehensible response to a 
cascade of several devices, red LED
flashes once

- Various sensor releases have been used 

(release 2, release 3 and US beam sensors)

- Only use US beam and/or release 3 sensors
- For US beam or release 3 sensors, switch synchronisa-

tion off and manually prevent any overlap

The red LED flashes 10 times

- Loss of power during parameterisation (memory error)

- Carry out initialisation on the master (sensor on the door

controller)

The green LED on the slave module

lights up permanently

- The master is in standby mode and the slave is not. Only the slave

was reactivated.

- Reactivate master using door activation
- Carry out initialisation on master 

(sensor on door controller)

- Check test input (parameter 1)
- Activate synchr. on all sensors (parameter 9)
- Replace ribbon cable if necessary

Troubleshooting

4

Technical data

5

Declaration of conformity, identification of the year of manufacture by means of the serial number

6

7

Contact

Bircher Reglomat AG
Wiesengasse 20
CH-8222 Beringen
www.bircher-reglomat.com

Technology 

Active infrared (triangulation)

Wavelength 

880 nm

Number of IR beams 

8, can be switched separately, synchronized

Dimensions of an IR beam 

30 mm x 60 mm at 2.2 m mounting height

Detection zone, dimensions 

471 mm x 60 mm at 2.2 m mounting height

Response time 

< 50 ms

Mounting height 

1.7 – 3.0 m, depending on the background

Angle setting 

2° – 14°, set in increments of 3°

Installation length in the profile 

300 mm incl. mounting clips

Power supply 

15 – 37 VDC/ 15 – 26 VAC, AC independently

Power consumption 

Max. 3.3 W, 0.17 W per beam

Making current 

< 500 mA

Test input 

4 versions (high/low active, pull up/down

Output 

Change-over relay, max. 40 VDC/40 VAC, 1 A

Hold intervals 

0 – 10 s (adjustable)

Operating temperature 

-20 °C bis 60 °C

Type of protection

IP54 suitable

Remote control range 

5 m

Number of devices that can be in-
terconnected 

4 units, synchronized

Application 

Stationary/moving presence detection

Functional safety level 

SIL2

4

Identification of the year of manufacture by means of the serial number

6.2

Green label:

Position of the green label on the US beam sensor:

Year of 

manufacture 

Week

Note: Carrying out master initialisation or switching the operating voltage off/on will reset an error.

Bircher Reglomat AG, Wiesengasse 20, CH-8222 Beringen
MD 2006/42/EG, RoHS 2011/65/EU, EMC 2014/30/EU
44/205/12/413806-001
TÜV NORD CERT, NB 0044

6.1

 

EC-Declaration of conformity

Manufacturer: 
Following directives have been observed:  
EC type-examination certificate:

 

Notified inspection centre:
Product variant: 

Usbeam, UniScan

Danish seller

Swissdoor ApS

Stenhuggervej 2

DK-5471 Soendersoe

www.swissdoor.dk

Tlf.: +45 86 28 00 00

[email protected]

Отзывы: