Changeover to simulations mode

Press «Sim1»
button

Press «Sim2»
button

Press «Sim2»
button

Press «Sim2»
button

Notes

Changeover to simulation mode:
Press the Sim1 + Sim2 buttons
simultaneously for 2 seconds.

Mode
Sim1

2 seconds

+

Data
Sim2

2 seconds

1

Simulation mode:

Activation of the loop

1

Data
Sim2

1

Mode
Sim1

2

Data
Sim2

2

L0 -

No loop activation (time functions are active) 

L1  -

Loop activation (time functions are active)

- Loop 1  

- Loop 2 

Activation of the output relay

Mode
Sim1

1

Data
Sim2

1

Mode
Sim1

2

Data
Sim2

2

0

0 - 

Activation of output 

0

1  - 

Activation of output

- Loop 1  

- Loop 2

Alarm output activation

Mode
Sim1

Data
Sim2

A0 

-Switch off alarm relay

A1  

-

Switch on alarm relay

Inductance of loop 1

Mode
Sim1

1

Measurement of the inductance, value in 

µH

Inductance of loop 2

Mode
Sim1

2

Measurement of the inductance, value in 

µH

Exiting simulation mode

Mode
Sim1

2 seconds

1

2

Return to function mode

If an error occurs, operating mode «A» and error display «E» light up alternately and an error code such as E 012 is displayed. The LED changes to
flashing red, the 4 most recent errors are stored and can be interrogated.

Display

E001

E002

E011

E012

E101

E102

E201/E202 E301

E302

E311

E312

Error

Interruption
Loop 1

Interruption
Loop 2 

Short circuit 
Loop 1

Short circuit
Loop 2

Under  -
voltage

Over-
voltage

Saving
error

Loop 1 
too large

Loop 2 
too large

Loop 1 
too small

Loop 2 
too small

Briefly pressing the «Data» button shows the last of 4 errors on the display. Another short press switches to the error before that, and so on. When
the button is pressed for the 5th time, the device switches back to automatic mode. If you press the «Data» button for 4 seconds during the query,
all error messages are deleted. The figure shows memory slot 1 in which error 001, Interruption loop 1, has been stored (example).

ProLoop2

Supply voltage / 
Power consumption

• 24 ACDC: 24 VAC -20 % to +10%, max. 2 VA

24 VDC -10 % to +20%, max. 1.5 W

• LVAC:

100-240 VAC ± 10%, 50/60 Hz, max. 2.9 VA

Loop inductance

max. 20 to 1000 µH, 
ideally 80 to 300 µH

Loop connection wiring

At 20-40 µH: max. 100 m at 1.5 mm

At >40 µH: max. 200 m with 1.5 mm

min. twisted 20x/m

Loop resistance

< 8 Ohm  with connection wire

Output relay (loop)

max. 240 VAC; 2 A / 30 VDC; 1 A; AC-1

Output relay (alarm)

max. 40 VACDC; 0.3 A; AC-1

Dimensions

22.5 x 94 x 88 mm (B x H x T)

Housing mounting

Direct DIN rail mounting

Connection type

Plug-in terminals

Protection class 

IP 20

Operating temperature

-20°C to +60°C

Storage temperature

-40°C to +70°C

Air humidity

<95% non-condensing

5

Simulation mode

6

Troubleshooting

7

Reset

8

Most important technical data

9

Declaration of conformity

10

Contact data

Mode
Sim1

2 seconds

Reset 1 (recalibration)

The loop(s) is/are recalibrated.

Mode
Sim1

8 seconds

Data
Sim2

Reset 2 (factory setting)

All values (except the error memory) are reset to the factory
settings (see Table 4.11a). The loop(s) is/are recalibrated.