2.
Installation
Cable types
№
Cable connection
Max. length
Type
1
Ethernet (IEEE 802.3)
100 m.
Four twisted pair cables of no lower than category five
with a wire size of no less than 0.2 mm
2
2
Power source
50 m.
Duplex cable with a wire size of no less than 0.75 mm
2
(for
example, 3192Y)
3
Turnstile, lock
20 m.
Duplex cable with a wire size of no less than 0.75 mm
2
(for
example, 3192Y)
4
Exit buttons, sensors
10 m.
CQR-6 or RAMCRO-6 cable
5
Wiegand interface
60 m.
Four twisted pair cables of no lower than category five
with a wire size of no less than 0.2 mm
2
General installation notes
Install the controller on vertical surface;
Cables must be installed in accordance with the operational code for electrical
installations;
Do not lay cables within 30 cm of sources of electromagnetic interference;
All cables must only intersect power cables at a right angle;
All cable extensions must be soldered.
Carefully check for mechanical damage on the surface of the controller circuit board and
case;
In order to avoid short circuits, the protected ends of cables used to connect the controller
must not exceed 5 mm.
Caution
BioSmart 5M-E should be protected from rain and water.