6.3 Alarm Signs 

AIR  BIO  Controller  for  solid  fuel  boilers  provides  for  situations  when  emergency 

messages might be sent: 

-

 

in case of «boiler overheat», when boiler temperature is more than +95ºС;  

-

 

in case of ignition in a screw feed, when temperature on the screw sensor is higher 

than the temperature set up in Item 7.4. 

-

 

in case of temperature sensor failure;  

Emergency Indicator lights up on the front panel, the Controller switches off the fan, 

and at the same time the central heating pump continues uninterrupted operation cooling the 
boiler  by  ducting  the  heat  carrier  through  the  central  heating  system.  As  well  as  AIR  BIO 
Controller  provides  for  hooking  up  the  external  alarm  system  that  will  create  closed-loop 
(unclosed-loop) in case of emergency situation.    

AIR  BIO  is  additionally  equipped  with  thermal  protection  sensor.  The  sensor  is 

intended for forced  switching  off  the forced-draft blower  and screw feed if the  heat  carrier 
reaches  abnormally  high  temperature  in  the  heating  circuit.  90  degrees  in  a  standard  way. 
Response tolerance is 10%.  

 

7 TECHNICAL MAINTENANCE 

 

7.1 Safety 

1.

 

Installation and operation of AIR BIO Controller shall be performed in accordance 

with fire safety regulations and electrical safety requirements. 

2.

 

Installation and adjustment of the Controller shall be carried out in the presence of 

the qualified specialist. 

3.

 

It is recommended to install the Controller on the boiler in such a way to prevent it 

from being dirtied and mechanically thermally damaged during boiler operation. 

4.

 

It  is  prohibited  to  use  the  Controller  beyond  the  operating  temperature  range 

specified in this Operation Manual. 

5.

 

It  is  prohibited  to  make  any  changes  in  the  Controller  construction  at  its  own 

discretion. 

6.

 

It is prohibited to locate the temperature sensor in fluids. 

7.

 

During  operation  it  is  necessary  to  ensure  that  there  are  no  any  contacts  of  wire 

insulation with boiler heating up elements. 

8.

 

Safety  appliance  shall  be  replaced  only  when  the  Controller  is  off  (disconnected 

from power supply network) and with the safety appliance having the nominal specified in 
this Operation Manual. 
 

7.2 Technical Maintenance Procedure 

When using the Controller, it is recommended to adhere to the following rules: 
-

 

it is recommended to hook up the unit using the surge arrester; 

-

 

it  is  recommended  to  clean  up  the  boiler  in  accordance  with  the  Boiler  Manual 

requirements; 

-

 

it is necessary to keep the unit away from moist environment and make sure that no 

water will go inside the unit; 

-

 

it is recommended to wipe clean of dust, when required; 

Содержание AIR BIO

Страница 1: ...1 OPERATION MANUAL FOR AIR BIO ELECTRONIC CONTROL UNIT FOR SOLID FUEL BOILER Kharkov city...

Страница 2: ...and fuel supply system AIR BIO delivery set includes 1 Network cable with plug tip 2 m long 1 ea 2 Wire for hooking up the fan with connector 0 5m long 1 ea 3 Wire for hooking up the pump 2m long 2 ea...

Страница 3: ...3 Picture1 AIR BIO Hookup Diagram Picture 2 AIR BIO Hookup to Central Heating System Diagram...

Страница 4: ...following advantages fuel significant saving because there is a capability to control burning intensiveness capability to adjust Hot Water Supply temperature capability to adjust Central Heating temp...

Страница 5: ...nector in intended to protect the unit from short circuit Control unit screen displays the boiler operation mode When entering the MENU it displays the menu items and modes for setting up the respecti...

Страница 6: ...tion time and interval time for fuel supply gear If boiler temperature is equal or higher than the preset temperature the Controller is in Standby mode Each Controller shall be adjusted individually d...

Страница 7: ...in Display When supplying power and pressing Power button the Controller LCD display will show the main page User Menu with the following information STANDBY t CH XX YY t HW XY YX ZZ screw t QQ Pictur...

Страница 8: ...ching off the pump check up of its operability 3 3 2 Firing ON OFF This function is intended for starting up the cold boiler When activating this function you transfer the boiler from Standby mode to...

Страница 9: ...when the boiler is in the mode of gaining temperature up to the preset value Delivery time Value is set up from 1 to 250 sec Delivery time is selected in accordance with boiler capacity fuel type and...

Страница 10: ...changes within the range of 30 95 b Pump Hysteresis changes within the range 1 10 3 3 7 Adjuster Menu This function allows adjusting basic parameters of the Controller s program 3 3 7 1 Screw feeder a...

Страница 11: ...em 3 3 9 Boiler Hysteresis Range 1 10 You set up the value up to which heat carrier operation temperature goes down from the preset temperature whereby the Controller will transfer the boiler from Sup...

Страница 12: ...temperature 45 9 Boiler hysteresis 5 5 PERFORMANCE DATA Parameter Description UoM Value 1 Power supply voltage V z 230 50 2 Max power input Watt 4 5 3 Automatic equipment operation temperature range 1...

Страница 13: ...troller central heating systems shall be equipped with safety valves operating under pressure surge tanks protective systems to ensure there will be no water boiling in the central heating system it i...

Страница 14: ...fire safety regulations and electrical safety requirements 2 Installation and adjustment of the Controller shall be carried out in the presence of the qualified specialist 3 It is recommended to insta...

Страница 15: ...is not less than 10 years 2 LTD Bioprom Company Kharkov provides warranty for AIR BIO Controller for the period of 18 months from the date of sale but not longer than 24 months from the date of manuf...

Страница 16: ...within the longer time period 9 TRANSPORTATION For the purpose of keeping maintaining the Controller integrity and proper functionality during transportation one shall follow all the transportation c...

Страница 17: ...a www bioprom kh ua www bioprom ua www bioprom kharkov ua For all issues relating to warranty and post warranty service please feel free to contact us at the address of 126 1 Plekhanovskaya Str Kharko...

Страница 18: ...18 For Notes...

Страница 19: ...19 For Notes...

Страница 20: ...oller is used in strict compliance with the manufacturer s specification Unit is checked by ______ Full Name ___________ signature Serial Number ______________________ Date Manufacturer s Signature an...

Отзывы: