DPM-500 Analog Input Meter Instruction Manual
47
Factory Defaults & User Settings
The following table shows the factory setting for most of the programmable parameters on the meter.
Parameter
Display
Default Setting
Input type
Input
4-20 mA
Dual-scale feature
d-SCAL
No (Single scale)
Filter
filter
70
Bypass
bypass
0.2
Function
Functn
Linear
Number of points
No Pts
2
Programming
prog
Scale
Input 1
InP 1
4.000 mA
Display 1
Dis 1
4.000
Input 2
InP 2
20.000 mA
Display 2
Dis 2
20.000
Decimal point
dd.ddd
3 places
Cutoff value
CutofF
0.000 (disabled)
Display assignment
Dsplay
Display Line 1
Line 1
PV: Process variable
Display Line 2
Line 2
Eng unit default= mA
Display intensity
d-Inty
8
Relay 1 action
Act 1
Automatic
Relay 1 set point
Set 1
1.000
Relay 1 reset point
RSt 1
0.500
Relay 2 action
Act 2
Automatic
Relay 2 set point
Set 2
2.000
Relay 2 reset point
RSt 2
1.500
Relay 3 action
Act 3
Automatic
Relay 3 set point
Set 3
3.000
Relay 3 reset point
RSt 3
2.500
Relay 4 action
Act 4
Automatic
Relay 4 set point
Set 4
4.000
Relay 4 reset point
RSt 4
3.500
Fail-safe relay 1
Fls 1
Off
Fail-safe relay 2
Fls 2
Off
Fail-safe relay 3
Fls 3
Off
Fail-safe relay 4
Fls 4
Off
On delay relay 1
On 1
0.0 sec
Off delay relay 1
Off 1
0.0 sec
On delay relay 2
On 2
0.0 sec
Off delay relay 2
Off 2
0.0 sec
On delay relay 3
On 3
0.0 sec
Parameter
Display
Default Setting
Off delay relay 3
Off 3
0.0 sec
On delay relay 4
On 4
0.0 sec
Off delay relay 4
Off 4
0.0 sec
Loop break relay 1
ignore
Ignore
Loop break relay 2
ignore
Ignore
Loop break relay 3
ignore
Ignore
Loop break relay 4
ignore
Ignore
Display 1 analog out
Dis 1
4.000
Output 1 value
Out 1
4.000 mA
Display 2 analog out
Dis 2
20.000
Output 2 value
Out 2
20.000 mA
Source analog output
Source
Process Variable
Overrange output
O-rang
21.000 mA
Underrange output
u-rang
3.000 mA
Loop break output
break
1.000 mA
Maximum output
mAx
23.000 mA
Minimum output
min
1.000 mA
Slave ID (Address)
SlavId
247
Baud rate
baud
9600
Transmit delay
Tr dly
50 ms
Parity
Parity
Even
Byte-to-byte timeout
t-byt
010 (0.1 sec)
F1 function key
F1
Reset max & min
F2 function key
F2
Line 1: Max (Hi)
F3 function key
F3
Acknowledge relays
F4 function
F4
Acknowledge relays
Digital input 1
dI 1
Menu
Digital input 2
dI 2
Right arrow
Digital input 3
dI 3
Up arrow
Digital input 4
dI 4
Enter
Digital output 1
dO 1
Alarm 1
Digital output 2
dO 2
Alarm 2
Digital output 3
dO 3
Alarm 3
Digital output 4
dO 4
Alarm 4
Password 1
Pass 1
000000 (unlocked)
Password 2
Pass 2
000000 (unlocked)
Password 3
Pass 3
000000 (unlocked)