DPM-500 Analog Input Meter Instruction Manual
7
F4 Digital Input
Logic Levels
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Relays
Rating
2 or 4 SPDT (Form C) internal and/or 4 SPST
(Form A) external; rated 3 A @ 30 VDC and
125/250 VAC resistive load; 1/14 HP (
≈
50 W)
@ 125/250 VAC for inductive loads
Noise
Suppression
Noise suppression is recommended for each
relay contact switching inductive loads; see
page 13 for details.
Deadband
0-100% of span, user programmable
High or Low
Alarm
User may program any alarm for high or low trip
point.
Unused alarm LEDs and relays may be disabled
(turn off).
Relay
Operation
Automatic (non-latching) and/or manual reset
Latching (requires manual acknowledge)
with/without clear
Pump alternation control (2 to 8 relays)
Sampling (based on time)
Off (disable unused relays and enable Interlock
feature)
Manual on/off control mode
Relay Reset
User selectable via front panel buttons or digital
inputs
1.
Automatic reset only (non-latching), when
the input passes the reset point.
2.
Aut manual reset at any time (non-
latching)
3.
Manual reset only, at any time (latching)
4.
Manual reset only after alarm condition has
cleared (latching)
Note: Front panel button or digital input may be
assigned to acknowledge relays
programmed for manual reset.
Time Delay
0 to 999.9 seconds, on & off relay time delays
Programmable and independent for each relay
Fail-Safe
Operation
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm
condition.
In case of power failure, relay will go to
alarm state.
Auto
Initialization
When power is applied to the meter, relays will
reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
Output Source
Process variable (PV), max, min, set points 1-8,
Modbus input, or manual control mode
Scaling Range
1.000 to 23.000 mA for any display range
Calibration
Factory calibrated: 4.000 to 20.000 = 4-20 mA
output
Analog Out
Programming
23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
Accuracy
± 0.1% of span ± 0.004 mA
Temperature
Drift
0.4 µA/
C max from 0 to 65
C ambient,
0.8 µA/
C max from -40 to 0
C ambient
Note: Analog output drift is separate from input drift.
Isolated
Transmitter
Power Supply
Terminals I+ & R: 24 VDC
10%. May be used to
power the 4-20 mA output or other devices.
Refer to Transmitter Supply Voltage Selection
(P+, P-) on page 10. All models rated @ 40 mA
max.
External Loop
Power Supply
35 VDC maximum
Output Loop
Resistance
Power supply Minimum
Maximum
24 VDC
10
700
35 VDC
(external)
100
1200
Modbus
®
RTU Serial Communications
Slave Id
1
– 247 (Meter address)
Baud Rate
300
– 19,200 bps
Transmit
Time Delay
Programmable between 0 and 199 ms
Data
8 bit (1 start bit, 1 or 2 stop bits)
Parity
Even, Odd, or None with 1 or 2 stop bits
Byte-To-Byte
Timeout
0.01
– 2.54 second
Turn Around
Delay
Less than 2 ms (fixed)
Note: Refer to the Modbus Register Tables located at
www.binmaster.com for details.
MeterView Pro
System
Requirements
Microsoft
®
Windows
®
XP/Vista/7/8/10
Communications
USB 2.0 (Standard USB A to Micro USB B)
Configuration
Configure meters one at a time