7
www.bindicator.com
VRF180913 Rev. A
7
Disconnects must meet the following requirements:
• Located in close proximity to the device
• Easily accessible to the operator
• Appropriately marked as the disconnect for the device and associated circuit
• Sized appropriately to the requirements of the protected circuit (See Specifications)
PROTECTIVE EARTH GROUND
To eliminate shock hazards in the unlikely event of an internal insulation breakdown, the unit is provided with
an “earth” lead which must be connected to earth ground. In addition, the input power ground lead must be
connected to the “protective earth” (
) terminal provided. Wire sizes must be selected such that it can safely
carry the sum total of all circuits’ maximum amperage.
CONDUIT-CABLE CONNECTION
Two threaded female conduit openings are provided in the housing for input and output wiring. When only one
conduit opening is used for installation, the unused opening must be sealed with a suitable type 4X/IP66 plug
with pipe sealant in order to maintain approval requirements.
ELECTRICAL CONNECTIONS
Note: The VRF II Series can be operated from 120-240 VAC 50/60 Hz or 24-48 VDC and provides reverse polarity
protection in the event of a wiring error.
VRF II SERIES INTEGRAL MODEL ONLY
Input Power Connections
1. Refer to Figures 3 or 4 and 5 when connecting input power to the unit.
2. Loosen the housing cover screws and remove cover.
CAUTION: IF THE UNIT WAS SUPPLIED WITH A GASKET AVOID FOLDING, CUTTING OR TEARING
GASKET. DAMAGING THE GASKET CAN ALLOW MOISTURE TO ENTER THE ENCLOSURE AND
DAMAGE THE UNIT.
Note: Two threaded female conduit openings are provided in the housing to separate input and output wiring.
3. Pull approximately 4” of cable through conduit closest to the grounding bracket and strip as follows:
a. Ground –
3
/
8
” (9 to 10 mm)
b. Power Leads –
1
/
4
” (6 to 7 mm)
4. Attach incoming ground lead to grounding bracket as shown in Figure 3 or 4.
Содержание VRF II Series
Страница 1: ...IOMVRF180713 Rev A VRF II Series Installation Operation Manual IOMVRF180913 Rev A ...
Страница 2: ......
Страница 24: ...20 VRF180913 Rev A www bindicator com 20 IX DIMENSIONAL DRAWINGS venture ...
Страница 25: ...21 www bindicator com VRF180913 Rev A 21 ...
Страница 26: ...22 VRF180913 Rev A www bindicator com 22 venture ...
Страница 27: ...23 www bindicator com VRF180913 Rev A 23 ...
Страница 28: ...24 VRF180913 Rev A www bindicator com 24 Optional Lights venture ...
Страница 29: ...25 www bindicator com VRF180913 Rev A 25 Optional Lights ...
Страница 30: ...26 VRF180913 Rev A www bindicator com 26 Notes ...
Страница 31: ...27 www bindicator com VRF180913 Rev A 27 Notes ...