IV.  MECHANICAL INSTALLATION

The following precautions should be observed when installing and operating an LP II device:

•  The installation and wiring of this product must comply with all national, federal, state, municipal and local codes 

that apply.

•  The LP II Series are precision devices - handle carefully to prevent damage to the rod.

•  Do not allow moisture to enter the electronics enclosure. Conduit should slope downward from the LP II housing. 

Install drip loops (or drain fitting) and seal conduit with silicone rubber product.

•  The resonant frequency of the rod is 400 Hz (±10%); locations subject to vibration frequencies greater than 100 

Hz should be avoided.

CAUTION:  WHEN MOUNTING UNITS, NEVER ADJUST THE ORIENTATION BY TURNING THE HOUSING. USE A  
WRENCH FOR PROCESS FITTING UNITS, OTHERWISE A STRAP WRENCH SHOULD BE USED TO TIGHTEN INTO PLACE.   
ATTEMPTING TO TIGHTEN THE UNIT BY ROTATING THE HOUSING OR ROD MAY DAMAGE THE UNIT 
AND VOID THE WARRANTY.

CAUTION:  WHETHER MOUNTING DIRECTLY THROUGH A SIDE WALL, OR PIPE EXTENDED AND 
MOUNTED VERTICALLY THROUGH THE TOP OF A VESSEL, NEVER ATTEMPT TO MOUNT THROUGH 
A FULL COUPLING.

WARNING: HIGH VOLTAGE IS PRESENT. REMOVE POWER FROM THE UNIT BEFORE INSTALLING, REMOVING, OR 
MAKING ADJUSTMENTS.

WARNING: IN ORDER TO MAINTAIN SAFE OPERATION IN HAZARDOUS LOCATIONS, THE INTEGRITY OF THE 
ALUMINUM CASTING AND THE ENVIRONEMENTAL SEALS MUST BE MAINTAINED. THE USER/INSTALLER 
MUST AVOID INSTALLATIONS WHERE AGGRESSIVE SUBSTANCES MAY BE PRESENT AND COULD AFFECT THE 
PERFORMANCE OF THESE MATERIALS. CARE MUST ALSO BE EXERCISED WHEN REMOVING AND REPLACING THE 
COVER, SO NO MARRING, SCRATCHING OR DAMAGE OCCURS TO THE FLANGES, AND THAT FLANGE SURFACES 
REMAIN COMPLETELY CLEANED OF DEBRIS. 

WARNING: FOR UNITS INSTALLED IN HAZARDOUS LOCATIONS, TO REDUCE THE RISK OF IGNITION OF HAZARDOUS 
ATMOSPHERES, CONDUIT RUNS MUST HAVE A SEALING FITTING CONNECTION WITHIN 18 IN. OF THE ENCLOSURE.

WARNING: FOR PRODUCTS MARKED AS TYPE 4X, USE TYPE 4X HUB FITTING; FOR IP66 USE IP66 HUB FITTING. 

GUIDELINES

Содержание LP II Series

Страница 1: ...Pulse PointTM II Series Vibrating Rod Installation Operation Manual IOM LVP180914 Rev D...

Страница 2: ......

Страница 3: ...nfiguration Installation Operation Manual CONTENTS I HANDLING STORAGE 1 II GENERAL SAFETY 2 III PRODUCT DESCRIPTION 3 IV MECHANICAL INSTALLATION 5 V ELECTRICAL INSTALLATION 7 VI SET UP 14 VII MAINTENA...

Страница 4: ...ES CONDITIONS OR PROCEDURES WHICH IF NOT FOLLOWED COULD RESULT IN SERIOUS INJURY RISK OF ELECTRICAL SHOCK CAUTION IDENTIFIES CONDITIONS OR PROCEDURES WHICH IF NOT FOLLOWED COULD RESULT IN SERIOUS DAMA...

Страница 5: ...AND RECYCLING This product can be recycled by specialized companies and must not be disposed of in a municipal collection site If you do not have the means to dispose of properly please contact for re...

Страница 6: ...warranty reasons use of accessory equipment not recommended by the manufacturer or modification of this device is explicitly forbidden All servicing of this equipment must be performed by qualified se...

Страница 7: ...eater than the set threshold determined by the sensitivity setting the alarm relay will turn ON or OFF depending on the fail safe settings APPLICATIONS Unlike radio frequency and capacitance technolog...

Страница 8: ...e Up to 6 seconds Time Delay ADVANCED Field Adjustable Up to 150 seconds Fail Safe Field Selectable high low level Sensitivity STANDARD Minimum 6 lbs ft3 96 kg m3 Field Adjustable Sensitivity ADVANCED...

Страница 9: ...THE HOUSING OR ROD MAY DAMAGE THE UNIT AND VOID THE WARRANTY CAUTION WHETHER MOUNTING DIRECTLY THROUGH A SIDE WALL OR PIPE EXTENDED AND MOUNTED VERTICALLY THROUGH THE TOP OF A VESSEL NEVER ATTEMPT TO...

Страница 10: ...used with powders it should be installed vertically or at a downward angle that exceeds the angle of repose to reduce material build up see figure 1 Figure 1 Mounting Orientation Do not mount the rod...

Страница 11: ...l equipment you should always follow basic safety precautions including the following The installation and wiring of this product must comply with all national federal state municipal and local codes...

Страница 12: ...240 VAC 50 60 Hz or 24 48 VDC and provides reverse polarity protection in the event of a wiring error LP II SERIES INTEGRAL MODEL ONLY Input Power Connections 1 Refer to Figures 3 or 4 and 5 when conn...

Страница 13: ...n connecting input power to the unit 2 Loosen set screw that locks cover in place 3 Unscrew the housing cover and remove Note Two threaded female conduit openings are provided in the remote housing to...

Страница 14: ...h conduit and strip 3 16 4 to 5 mm 18 Connect factory supplied cable to terminal board as shown in Figure 10 19 Check that all wires are held tightly in place by lightly pulling each conductor 20 Repl...

Страница 15: ...THE GASKET CAN ALLOW MOISTURE TO ENTER THE ENCLOSURE AND DAMAGE THE UNIT Figure 4 LP II Integral Enclosure with Cover Removed ADVANCED Figure 5 Power and Ground Connections Figure 6 Main Relay Connec...

Страница 16: ...D www bindicator com Figure 8 LP II Remote Enclosure with Cover Removed STANDARD Figure 9 LP II Remote Enclosure with Cover Removed ADVANCED Note 1 For safety properly ground the enclosure to an adequ...

Страница 17: ...13 www bindicator com LVP180914 Rev D Figure 10 LP II Remote Connection Diagram...

Страница 18: ...will discuss configuration for optimum performance in a given application The settings are controlled by SW1 as shown in Figure 11 PRODUCT OVERVIEW ADVANCED MODEL Figures 4 and 9 show the electronics...

Страница 19: ...rm LED is ON Non Alarm State material below the rod Main Relay is energized Relay NC contacts are open Relay NO contacts are closed Alarm LED is OFF Note If the electrical power fails the main relay t...

Страница 20: ...or its absence and the output relay changes state is field programmable using SW5 Positions 2 and 3 The delay can be for when the product touches the rod or when the product leaves the rod or both reg...

Страница 21: ...s factory set for the lowest sensitivity The table below is for illustration purposes of a vertically mounted unit only and results will vary depending on material properties and conditions SW3 Sensit...

Страница 22: ...in the table below WARNING TO AVOID IGNITION HAZARD DUE TO ELECTROSTATIC DISCHARGE CLEAN ONLY WITH A DAMP CLOTH WARNING IN ORDER TO MAINTAIN SAFE OPERATION IN HAZARDOUS LOCATIONS THE INTEGRITY OF THE...

Страница 23: ...Ensure the cover is properly torqued and unit is installed wrench tight CODE CONDITION RELAYS 1 No or low excitation to the rod Aux Relay De energized Alarm Relay De energized 2 No return signal from...

Страница 24: ...150 Venture Boulevard Spartanburg SC 29306 Tel 800 778 9242 Fax 864 574 8063 sales bindicator com www bindicator com 2016 All rights reserved All data subject to change without notice LVP180914 Rev D...

Отзывы: