7. Refer to Figures 3 or 4 and 6 when connecting to the main relay.
8. Pull approximately 4.5” (11.43 cm) of cable through conduit and strip
1
/
4
” (6 to 7 mm).
9. Attach leads to terminal block as shown in Figure 6. (3.5 in-lb, 0.4 N-m)
10. Check that all wires are held tightly in place by lightly pulling each conductor.
For STANDARD models skip to Step 15; for ADVANCED models continue to Step 11.
Auxiliary Relay Connections - ADVANCED MODEL ONLY
11. Refer to Figures 4 and 7 when connecting to the auxiliary relay.
12. Pull approximately 5.5” (13.97 cm) of cable through conduit and strip
1
/
4
” (6 to 7 mm).
13. Attach leads to terminal block as shown in Figure 7. (2.0 in-lb, 0.23 N-m)
14. Check that all wires are held tightly in place by lightly pulling each conductor.
15. Reinstall the gasket, if necessary.
16. Replace cover and tighten screws to 60 in-lb (6.8 N-m) of torque.
LP II SERIES REMOTE MODEL ONLY
Input Power Connections
1. Refer to Figures 8 or 9 and 5 when connecting input power to the unit.
2. Loosen set screw that locks cover in place.
3. Unscrew the housing cover and remove.
Note: Two threaded female conduit openings are provided in the remote housing to separate input and output wiring
from the remote rod wiring.
4. Pull approximately 6” (15.24 cm) of cable through conduit closest to grounding bracket and strip as
follows:
a. Ground –
3
/
8
” (9 to 10 mm)
b. Power Leads –
1
/
4
” (6 to 7 mm)
5. Attach incoming ground lead to grounding bracket as shown in Figure 5.
Note: The LP II incorporates pluggable terminal blocks for ease of connection. If the terminal block is unplugged while
making connections, ensure it is seated properly when reinstalled.
6. Attach power leads to terminal block as shown in Figure 8 or 9. (3.5 in-lb, 0.4 N-m)
7. Check that all wires are held tightly in place by lightly pulling each conductor.
Main Relay Connections
8. Refer to Figures 8 or 9 and 6 when connecting to the main relay.
9. Pull approximately 9” (22.86 cm) of cable through conduit and strip
1
/
4
” (6 to 7 mm).
10. Attach leads to terminal block as shown in Figure 6. (3.5 in-lb, 0.4 N-m)
11. Check that all wires are held tightly in place by lightly pulling each conductor.