FAIL-SAFE SELECTION

The LP II is factory set for high level fail-safe operation. The Fail-Safe is controlled by SW1, position 1 on Standard units; 
SW5, position 1 for Advanced units. Refer to Figure 13 to determine the Fail-Safe mode that suits your application.

Figure 13. Fail-Safe Operation

HIGH LEVEL FAIL-SAFE OPERATION (DEFAULT)
DIP Switch Settings
   • STANDARD: SW1-1 is OFF
   • ADVANCED: SW5-1 is OFF

Alarm State (material above the rod)
 

  •  Main Relay is de-energized

 

      Relay NC contacts are closed

 

      Relay NO contacts are open

 

  •  Alarm LED is ON

Non-Alarm State (material below the rod)
 

  •  Main Relay is energized

 

      Relay NC contacts are open

 

      Relay NO contacts are closed

 

  •  Alarm LED is OFF

Note: If the electrical power fails, the main relay turns OFF, giving the same indication 

as if material is above the rod. 

LOW LEVEL FAIL-SAFE OPERATION
DIP Switch Settings
   • STANDARD: SW1-1 is ON
   • ADVANCED: SW5-1 is ON

Alarm State (material below the rod)
 

  •  Main Relay is de-energized

 

      Relay NC contacts are closed

 

      Relay NO contacts are open

 

  •  Alarm LED is ON

Non-Alarm State (material above the rod)
 

  •  Main Relay is energized

 

      Relay NC contacts are open

 

      Relay NO contacts are closed

 

  •  Alarm LED is OFF

Note: If the electrical power fails, the main relay turns OFF, giving the same indication 

as if material is below the rod.

Содержание LP II Series

Страница 1: ...Pulse PointTM II Series Vibrating Rod Installation Operation Manual IOM LVP180914 Rev D...

Страница 2: ......

Страница 3: ...nfiguration Installation Operation Manual CONTENTS I HANDLING STORAGE 1 II GENERAL SAFETY 2 III PRODUCT DESCRIPTION 3 IV MECHANICAL INSTALLATION 5 V ELECTRICAL INSTALLATION 7 VI SET UP 14 VII MAINTENA...

Страница 4: ...ES CONDITIONS OR PROCEDURES WHICH IF NOT FOLLOWED COULD RESULT IN SERIOUS INJURY RISK OF ELECTRICAL SHOCK CAUTION IDENTIFIES CONDITIONS OR PROCEDURES WHICH IF NOT FOLLOWED COULD RESULT IN SERIOUS DAMA...

Страница 5: ...AND RECYCLING This product can be recycled by specialized companies and must not be disposed of in a municipal collection site If you do not have the means to dispose of properly please contact for re...

Страница 6: ...warranty reasons use of accessory equipment not recommended by the manufacturer or modification of this device is explicitly forbidden All servicing of this equipment must be performed by qualified se...

Страница 7: ...eater than the set threshold determined by the sensitivity setting the alarm relay will turn ON or OFF depending on the fail safe settings APPLICATIONS Unlike radio frequency and capacitance technolog...

Страница 8: ...e Up to 6 seconds Time Delay ADVANCED Field Adjustable Up to 150 seconds Fail Safe Field Selectable high low level Sensitivity STANDARD Minimum 6 lbs ft3 96 kg m3 Field Adjustable Sensitivity ADVANCED...

Страница 9: ...THE HOUSING OR ROD MAY DAMAGE THE UNIT AND VOID THE WARRANTY CAUTION WHETHER MOUNTING DIRECTLY THROUGH A SIDE WALL OR PIPE EXTENDED AND MOUNTED VERTICALLY THROUGH THE TOP OF A VESSEL NEVER ATTEMPT TO...

Страница 10: ...used with powders it should be installed vertically or at a downward angle that exceeds the angle of repose to reduce material build up see figure 1 Figure 1 Mounting Orientation Do not mount the rod...

Страница 11: ...l equipment you should always follow basic safety precautions including the following The installation and wiring of this product must comply with all national federal state municipal and local codes...

Страница 12: ...240 VAC 50 60 Hz or 24 48 VDC and provides reverse polarity protection in the event of a wiring error LP II SERIES INTEGRAL MODEL ONLY Input Power Connections 1 Refer to Figures 3 or 4 and 5 when conn...

Страница 13: ...n connecting input power to the unit 2 Loosen set screw that locks cover in place 3 Unscrew the housing cover and remove Note Two threaded female conduit openings are provided in the remote housing to...

Страница 14: ...h conduit and strip 3 16 4 to 5 mm 18 Connect factory supplied cable to terminal board as shown in Figure 10 19 Check that all wires are held tightly in place by lightly pulling each conductor 20 Repl...

Страница 15: ...THE GASKET CAN ALLOW MOISTURE TO ENTER THE ENCLOSURE AND DAMAGE THE UNIT Figure 4 LP II Integral Enclosure with Cover Removed ADVANCED Figure 5 Power and Ground Connections Figure 6 Main Relay Connec...

Страница 16: ...D www bindicator com Figure 8 LP II Remote Enclosure with Cover Removed STANDARD Figure 9 LP II Remote Enclosure with Cover Removed ADVANCED Note 1 For safety properly ground the enclosure to an adequ...

Страница 17: ...13 www bindicator com LVP180914 Rev D Figure 10 LP II Remote Connection Diagram...

Страница 18: ...will discuss configuration for optimum performance in a given application The settings are controlled by SW1 as shown in Figure 11 PRODUCT OVERVIEW ADVANCED MODEL Figures 4 and 9 show the electronics...

Страница 19: ...rm LED is ON Non Alarm State material below the rod Main Relay is energized Relay NC contacts are open Relay NO contacts are closed Alarm LED is OFF Note If the electrical power fails the main relay t...

Страница 20: ...or its absence and the output relay changes state is field programmable using SW5 Positions 2 and 3 The delay can be for when the product touches the rod or when the product leaves the rod or both reg...

Страница 21: ...s factory set for the lowest sensitivity The table below is for illustration purposes of a vertically mounted unit only and results will vary depending on material properties and conditions SW3 Sensit...

Страница 22: ...in the table below WARNING TO AVOID IGNITION HAZARD DUE TO ELECTROSTATIC DISCHARGE CLEAN ONLY WITH A DAMP CLOTH WARNING IN ORDER TO MAINTAIN SAFE OPERATION IN HAZARDOUS LOCATIONS THE INTEGRITY OF THE...

Страница 23: ...Ensure the cover is properly torqued and unit is installed wrench tight CODE CONDITION RELAYS 1 No or low excitation to the rod Aux Relay De energized Alarm Relay De energized 2 No return signal from...

Страница 24: ...150 Venture Boulevard Spartanburg SC 29306 Tel 800 778 9242 Fax 864 574 8063 sales bindicator com www bindicator com 2016 All rights reserved All data subject to change without notice LVP180914 Rev D...

Отзывы: