PRODUCT SAFETY INFORMATION
WARNING
1.
Meter assembly, interconnect cable assembly, and live line tool
adapters shall be considered
non-insulating
. Do not let live line tool
fittings come in contact with energized or grounded conductors.
The
live line tool adapters, fittings, and handles supplied with meters
shall not be used on any other devices.
2.
Use appropriate length live line tools for voltage being worked and
maintain minimum approach distances as outlined in OSHA
1910.269, Table R-6.
3.
All Phasing Meters and Voltage Detectors manufactured during and
after
2007 will have a limit mark engraved on the high voltage
probe(s) 2.5 inches from the tip to indicate to the user the physical
limit that should not be exceeded when approaching and contacting
an electrical conductor or other electrical test points. Zero Ohm
insulated adapters (81280IE) should be used if limit mark will be
exceeded.
4.
This equipment should be used only by qualified employees, trained
in and familiar with the safety-related work practices, safety rules
and other safety requirements associated with the use of this type
of equipment.
5.
These instructions are not intended as a substitute for adequate
training, nor do they cover all details or situations which could be
encountered when operating this type of equipment.
6.
Before operating this equipment, read, understand and follow all
instructions contained in this manual. Keep instructions with
equipment.
INSPECTION & MAINTENANCE BEFORE USE
WARNING
1.
Prior to using any high voltage test equipment a careful inspection
should be made to ensure the unit is free from any contaminants
such as dirt, grease, etc. and that there are no apparent physical
damages.
2.
High voltage probe assemblies shall be wiped clean prior to each use
with a silicone impregnated cloth and kept clean and free of
contaminants. This will prevent tracking on the outside of the probe
and meter error.
3.
Always confirm internal battery voltage before and after each use.
4.
Unit shall be tested before and after each use on a known voltage
source. Failure to do so could result in false negative indications
Содержание Phasing Ranger 2