NOTICE

   Important safety message relating to equipment 

damage only.

 

PRODUCT SAFETY INFORMATION 

 

WARNING

 

1.

 

Meter assembly, interconnect cable assembly, and live line 
tool adapters shall be considered 

non-insulating

. Do not let 

live line tool fittings come in contact with energized or 
grounded conductors.  

The live line tool adapters, fittings, 

and handles shall not be used on any other devices. 

2.

 

Use appropriate length live line tools for voltage being worked 
and maintain minimum approach distances as outlined in 
OSHA 1910.269, Table R-6. 

3.

 

All Phasing Meters and Voltage Detectors manufactured 
during and after

 

2007 will have a limit mark engraved on the 

high voltage probe(s) 2.5 inches from the tip to indicate to the 
user the physical limit that should not be exceeded when 
approaching and contacting an electrical conductor or other 
electrical test points.  Zero Ohm insulated adapters (81280IE) 
should be used if limit mark will be exceeded.

 

4.

 

This equipment should be used only by qualified employees, 
trained in and familiar with the safety-related work practices, 
safety rules and other safety requirements associated with the 
use of this type of equipment. 

5.

 

These instructions are not intended as a substitute for adequate 
training, nor do they cover all details or situations which could 
be encountered when operating this type of equipment. 

6.

 

Before operating this equipment, read, understand and follow 
all instructions contained in this manual.  Keep instructions 
with equipment. 

 

INSPECTION & MAINTENANCE BEFORE USE 

 

WARNING

 

1.

 

Prior to using any high voltage test equipment a careful 
inspection should be made to ensure the unit is free from any 
contaminants such as dirt, grease, etc. and that there are no 
apparent physical damages. 

2.

 

High voltage probe assemblies shall be wiped clean prior to 
each use with a silicone impregnated cloth and kept clean and 