User’s Manual UPSI-2403
2 Technical Data of the DC UPS UPSI-2403
T e c h n i c a l d a t a
Input voltage
24 V DC (22.5…28 V)
Input current
6.7 A max.
Output voltage
In normal mode: app. 0.5 V below input voltage
In battery mode: app. 29…19 V DC
Output current
6 A max.
Battery charge current
0.65 A max. (internal battery charger)
Charging method
UI characteristic, with temperature regulation
Protection
Deep dircharge protection: 19 V DC ±2 %
Overload protection at output: 9 A for 2 seconds, switch off
Short-circuit protection: Switch off via µC
Transfer time / limits
Mains / battery 20 V DC ±2 %, batteriy / mains 22 V DC ±2 %
Interface
USB (Standard B)
Type of battery
Equipped lead-gel-battery, maintenance-free, 1.3 Ah
Safety / EMC
CE
Temperature
Operating: 0…+40 °C / Storage: -10…+40 °C
Humidity
Operating: 10…85 % RH, non-condensing
Storage: 10…90 % RH, non-condensing
Dimensions (W x D x H)
90 x 100 x 121 ±0.5 mm
Weight (net)
2 kg
P r o d u c t s p e c i f i c d a t a
LED display
3-colour-LED for „Power ok” (green), „Power Fail” (orange),
„Battery low” (red/orange flashing) and „Battery defect”
(red/green flashing), short circuit at output/overload (red)
Battery monitoring
Battery test is carried out in normal mode approx every 10 minutes,
in case of “Battery defect“ notification the LED flashes red/green
Power consumption
App. 80 mA
Shutdown-suppression
During system start-up the shutdown signal is suppressed for app. 2 min.,
because any interface testing of Windows and a simultaneous power
failure would switch off the module. This suppression is only active when
the module is switched on the first time!
Reboot function
If power fails and then returns during the shutdown mode of Windows®,
the operating system will ‚lock‘ with the message „Your PC is now safe“.
The reboot function restarts the system after about 10 seconds.
Back up time
App. 33 min at 1 A / app. 9 min at 3 A / app. 3.5 min at 5 A
(measured at +20 °C)
The service life of the batteries is app. 4…5 years at +20 °C and will decrease by half with each temperature increase of 10 °C according
to EUROBAT.
Содержание UPSI-2403
Страница 1: ...Benutzerhandbuch User s Manual UPSI 2403 Deutsch English UPSI 2403 24 V 6 A...
Страница 2: ...Benutzerhandbuch UPSI 2403 2 Deutsch UPSI 2403 DC USV System...
Страница 13: ...Benutzerhandbuch UPSI 2403 13 Deutsch Notizen...
Страница 14: ...14 English User s Manual UPSI 2403 UPSI 2403 DC UPS System...
Страница 25: ...25 English User s Manual UPSI 2403 Notes...