- 67 -
INST
ALLA
TION
COMMISSIONING
displayed, wait for the number programmed
to flash (Fig. 7.14).
Fig. 7.14
• To exit programming, press button .
7.11 Setting the K coefficient of the
external temperature probe
The boiler is set with a K coefficient equal to
zero for boiler functioning without the probe
connected.
If the boiler is
NOT EQUIPPED
with the re-
mote control (optional) refer to Fig. 7.15.
Fig. 7.15
External temperature °C
20
20
15
10
5
0
-5
-10 -15 -20 -25
30
40
50
60
70
80
C.h. flow temperature °C
K=6 K=4 K=3
K=2
K=1,5
K=1
K=0,5
If the boiler is
EQUIPED
with the remote con-
trol (optional) refer to Fig. 7.16.
In this case K setting must be done from the
remote control.
Fig. 7.16
External temperature °C
20
20
15
10
5
0
-5
-10 -15 -20 -25
30
40
50
60
70
80
C.h. flow temperature °C
K=6 K=4
K=3
K=2
K=1,5
K=1
K=0,5
The K coefficients is a parameter that increas-
es or reduces the boiler flow temperature
when the outside temperature changes.
When installing the external probe it is neces-
sary to set this parameter based on the effi-
ciency of the heating plant in order to optimise
the flow temperature (Fig. 7.16).
E.g. In order to have a flow temperature at the
heating plant of 60°C with an external tem-
perature of -5°C, set a K at 1.5 (sectioned line
in Fig. 7.16).
Sequence for setting the K coefficient
• Enter in "programming mode" by pressing
keys 14 - 17 - 18 (Fig. 7.17) for 10 seconds
at the same time until the letters
P01
are
displayed on the LCD display, indicating
that "parameter 01, has been activated (Fig.
7.18).