BFT VISTA SW SXL Скачать руководство пользователя страница 13

D812034 00100_03

VISTA

 

SW

 

SXL

   

 

 

  -  13

ENGLISH

INSTALLATION MANUAL

PARAMETER

DEFINITION

MIN. MAX. DEFAULT

CUSTOM

DESCRIPTION

16

Auxiliary input 2 

configuration

0

12

1

 

0 = Input configured as Disabled opening

1 = Input configured as Emergency opening

2 = Input configured as Interlock door with priority

3 = Input configured as Interlock door without priority 

4 = Input configured as Lock Release Feedback

5 = Input configured as Lock release

6 = Input configured as Single Command with Master/Slave operating mode

7 = Input configured as Standby. If activated, it sets the door to standby only 

with the door in the closed position.
8 = Input configured as wake up from Standby. If activated, it restores 

operation following a Standby
9 = Input configured as step-by-step command, meaning that with a pulse 

the door opens and stays open, standing by for another pulse to close, again 

with the use of Int. Radar or Ext. Radar
10 = input configured as Temporary Stand By. If activated, the door is in stand 

by and therefore the closing movement is spring-loaded.  If deactivated, the 

door works normally. 

11 = Input configured as manual operation. If active, the operation of the 

selector in the head is disabled.

12 = Input configured as Stop Closed operation. If active, the operation of the 

selector in the head is disabled.

17

Auxiliary output 1 

configuration

0

5

0

 

0 = Output configured as Sensor supervision

1 = Output configured as Interlock

2 = Output configured as Door State open.

3 = Output configured as Door State closed.

4 = Output configured as Fault

5 = Output configured as Lock command repeat

18

Auxiliary output 2 

configuration

0

5

1

 

0 = Output configured as Sensor supervision
1 = Output configured as Interlock
2 = Output configured as Door State open.
3 = Output configured as Door State closed.
4 = Output configured as Fault
5 = Output configured as Lock command repeat

19

Not used

0

0

0

 

Not used, must be kept at = 0

20

Safety disabling angle 

during opening [%]

0

40

0

 

Safety disabling angle during opening, percentage of total travel

21

Master/Slave Connection 

Opening Time Lag [s]

0

100

0

 

Slave motor opening delay time with respect to master motor. 100ms 

increments

22

Master/Slave Connection 

Closing Time Lag [s]

0

100

0

 

Master motor closing delay time with respect to slave motor. 100ms steps

23

PHOT OPEN input 

polarity

0

1

1

 

0 = N.O. Normally open
1 = N.C. Normally closed

24

PHOT CLOSE input 

polarity

0

1

1

 

0 = N.O. Normally open
1 = N.C. Normally closed

25

KEY input polarity

0

1

1

 

0 = N.O. Normally open
1 = N.C. Normally closed

26

RADAR EXT input 

polarity

0

1

0

 

0 = N.O. Normally open
1 = N.C. Normally closed

27

RADAR INT input polarity

0

1

0

 

0 = N.O. Normally open
1 = N.C. Normally closed

28

AUX-IN 1 input polarity

0

1

0

 

0 = N.O. Normally open

1 = N.C. Normally closed

Содержание VISTA SW SXL

Страница 1: ...POUR PORTES AUTOMATICTUREN AUTOMATIZACIONES PARA PUERTAS AUTOMATISERINGSSYSTEMEN DEUREN Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully Attention Veui...

Страница 2: ...TTRICO ELECTRICAL SYSTEM SETUP PR DISPOSITION DE L INSTALLATION LECTRIQUE VORBEREITUNG DER ELEKTISCHEN ANLAGE PREPARACI N DE LA INSTALACI N EL CTRICA VOORBEREIDINGVAN DE ELEKTRISCHE INSTALLATIE A VIST...

Страница 3: ...on in dotazione Not supplied Ne sont pas fournis Nicht im lieferum No asignadas en el equipamiento base Niet meegeleverd 2 Non in dotazione Not supplied Ne sont pas fournis Nicht im lieferum No asigna...

Страница 4: ...As reductiemotor Traversa Header Entretoise Quertr ger travesa o Dwarsdrager Asse cerniera Hinge axis Axe charni re Achse des Scharniers Eje bisagra Scharnieras R1 V1 D3 D4 D5 Braccio rigido Single l...

Страница 5: ...rniers Eje bisagra Scharnieras L 22 27 55 56 292 5 Attacco anta Door leaf Attachment fitting Raccord vantail Fijaci n hoja Bevestiging deur 220 Asse motoriduttore Gearmotor Axis Axe motor ducteur Achs...

Страница 6: ...frein 9 Connecteur transformateur 10 Connecteur interrupteur ON OFF 11 Connecteur interrupteur s lections logiques 12 Connecteur encodeur 13 Connecteur moteur 14 S lecteur types de bras 15 Connecteur...

Страница 7: ...apteurs d tection s curit avec v rification la fermeture Verbindung Sensoren Erfassung Sicherheit mit berpr fung bei Schlie ung Conexi n sensores detecci n seguridad con control en fase de cierre Aans...

Страница 8: ...e sans priorit Karte Ohne Vorrang Tarjeta sin prioridad Kaart zonder voorrang 15 3 17 1 Togliere Jumper Remove jumper Retirer Cavalier Jumper entfernen Quitar el Jumper Jumper verwijderen U AA AB MAST...

Страница 9: ...must be suitably protected Install any fixed controls in a position where they will not cause a hazard away from moving parts More specifically hold to run controls must be positioned withindirectsig...

Страница 10: ...e spring to level 4 for VISTA SW SXL only 7 2 INSTALLING THE DOUBLE LEVER ARM Fig E E1 Fasten the arm to the leaf E2 Assemble the arm and fasten it to the actuator s output shaft E3 Adjust the spring...

Страница 11: ...inuous operation VISTA SW MXL ON Panic opening 7 Operating mode 2 OFF VISTA SW SXL OFF No reopen ing when obstacle is detected dur ing spring operated closing VISTA SW SXL ON Reopening when obsta cle...

Страница 12: ...elay after lock release 0 9 2 The time depends on the solenoid lock type Pulse mode with relock when door closes again 50 500 ms Magnetic Fail safe 200 to 2000 ms Motorized 500 to 5000 ms Pulse mode w...

Страница 13: ...selector in the head is disabled 17 Auxiliary output 1 configuration 0 5 0 0 Output configured as Sensor supervision 1 Output configured as Interlock 2 Output configured as Door State open 3 Output co...

Страница 14: ...ease the ENT key 5 When acquisition is done confirm sensors detected with ENT or press ESC to cancel 13 DOOROPERATINGMODE WithVISTASELorlogicselectionswitch Fig O EXTERNAL RADAR Only the RADAR EXT inp...

Страница 15: ...operation when there is no mechanical stop Every time the system is switched back on RESET operation when the first command is given the automatic door operator will try to reach the fully open posit...

Страница 16: ...he SLAVE board set parameter 13 2 CAUTION the two automatic door operators must be connected on the same power supply branch and no switches or fuses must be placed between the two operators Periphera...

Отзывы: