6.6) Self-diagnosis Menu (

selftest

)

Allows you to carry out control unit self-diagnosis.
If, at the end of the diagnosis, the answer is OK, it means that the control
unit and connected devices operate correctly.
In case of error, the display indicates the number of the terminal which does
not operate correctly; thus proceed to checking the devices connected to
this, making reference to the following table:
22

Start error

23

Stop error

24

Photocell error

25

Opening limit-switch error

26

Closing limit-switch error

27

Pedestrian input error

28

Open error

29

Close error

30

Electric edge error

31

Clock error

6.7) Autoset Menu (

Autoset

)

Allows you to automatically set the following parameters:
Opening torque
Closing torque
Encoder
Brake
To carry out autosetting, connect two N.O. pushbuttons, if not provided, to
inputs 21-28 (Open) and 21-29 (Close).

WARNING!!

The autoset operation is only to be carried out after checking

the  exact  leaf  (opening/closing)  movement,  and  correct  limit-switch
activation.
Therefore, during display of the (.... .... ....) message, carry out about fifteen
opening and closing manoeuvres in 

Hold-to-run

 mode, by pressing and

keeping the OPEN or CLOSE pushbutton alternatively pressed until the
opening or closing limit switches are activated.
During this phase, the control panel carries out tests with various levels of
opening/closing torque, encoder sensitivity and brake value.
Moreover, during autosetting, the leaf may be stopped, due to the checks
which are being carried out by the control panel.
After  this,  if  autosetting  is  successfully  completed,  the  control  unit
automatically exits the (.... .... ....) phase, and displays the 

OK

 message

which indicates correct autoset execution.
If, on the other hand, the control unit remains in the (.... .... ....) phase after
the 15 expected manoeuvres, it means that there are certain resistance
points along the gate which do not allow the control unit to set optimum
operation values.
Proceed to find out whether there are any mechanical obstructions which
might prevent regular leaf movement.

WARNING!

About 10 manoeuvres are carried out in 

Hold-to-run

 mode in

the course of the autoset phase, during which the installer must control the
automation movement and prevent persons or things from approaching or
standing within the automation working range.

WARNING: Check that the impact force value measured at the
points established by the EN 12445 standard is lower than that
specified in the EN 12453 standard.

Incorrect sensitivity setting can cause injuries to persons or
animals, or damage to things.

6.8) Statistics

Having connected the UNIPRO programmer to the control unit, enter the
CONTROL UNIT / STATISTICS menu and scroll the screenful showing the
statistical parameters:
-

Board microprocessor software version.

-

Number of cycles carried out. If motors are replaced, count the number
of manoeuvres carried out up to that time.

-

Number of cycles carried out from the latest maintenance operation.
It is automatically set to zero after each self-diagnosis or parameter writing.

-

Date of latest maintenance operation. To be updated manually from the
appropriate menu 

Update maintenance date

.

-

Installation  description.  16  characters  can  be  entered  for  installation
identification.

7) SERIAL CONNECTION (Fig.5)

The

LEO

 control panel allows several automation units to be connected in

a centralised way by means of appropriate serial inputs and outputs. This
makes it possible to use one single command to open and close all the
automation units connected.

Following the diagram in Fig. 5,  proceed to connecting all the 

LEO

 control

panels, exclusively using a telephone-type line.
Should  a  telephone  cable  with  more  than  one  pair  be  needed,  it  is
indispensable to use wires from the same pair.
The length of the telephone cable between one appliance and the next must
not exceed 250 m.
At  this  point,  each  of  the 

LEO

  control  panels  must  be  appropriately

configured, by setting a MASTER unit first of all, which will have control over
all the others, to be necessarily set as SLAVE (see logic menu).
Also set the Zone number (see parameter menu) between 0 and 127.

The zone number allows you to create groups of automation units,
each one answering to the Zone Master unit.

 Each zone can only be

assigned one Master unit, the Master unit in zone 0 also controls the Slave
units in the other zones.
Loop closing of the serial connection (indicated by a dotted line in Fig.5) is
only needed if you require to check the no. of the connected devices by
means of UNIPRO.

7.1) Opposite sliding leaves (Fig. 6)

Serial connection also provides centralized control of two opposite
sliding gates (Fig. 6a).
In this case, the Master M1 control board will perform closing and opening
of Slave M2 control board simultaneously.
In case of opposite sliding leaves, the M1 (master) control board and the M2
(slave)  control  board  should  bear  the  same  area  number  without  other
devices being connected in such area.
If  the  opening  direction  of  one  of  the  two  motors  is  incorrect,  invert  the
connection 6 and 8  of the motor as well as the connections 25 and 26 of
the opening and closing limiting devices.
The safety devices (photocells and sensing edges) should be connected
according to the diagram in Fig. 6b.
The  Start,  Open,  Close,  push-buttons  and  the  Timer  contact  should  be
normally connected to the M1 (master) control board.
The pedestrian command is to be connected to the M2 panel (slave).
The Stop command provides greater safety and is generated by a double
contact NC push-button connected to both control boards as shown in Fig. 6b.

NOTE:

Disable the TCA function from the M2 (slave) panel.

8) SCRAPPING
Warning:  This  operation  should  only  be  carried  out  by  qualified
personnel.

 Materials must be disposed of in conformity with the current

regulations. In case of scrapping, the automation devices do not entail any
particular risks or danger.  In case of materials to be recycled, these should be
sorted out by type (electrical components, copper, aluminium, plastic etc.).

9) DISMANTLING
Warning:  This  operation  should  only  be  carried  out  by  qualified
personnel.

When the control unit is disassembled to be reassembled on

another site

,

 proceed as follows:

Disconnect the power supply and the entire electrical installation.

In the case where some of the components cannot be removed or are
damaged, they must be replaced.

The descriptions and illustrations contained in the present manual
are not binding. The Company reserves the right to make any alterations
deemed appropriate for the technical, manufacturing and commercial
improvement  of  the  product,  while  leaving  the  essential  product
features unchanged, at any time and without undertaking to update
the present publication.

D811327_03

LEO

LEO

CONTROL UNITS

CONTROL UNITS

Содержание LEO

Страница 1: ...LEO CONTROL UNIT FOR ICARO D80000 00 00 99 Vers 00 ...

Страница 2: ... case of emergency Do not allow persons or children to remain in the automation operation area Keep radio control or other control devices out of children s reach in order to avoid unintentional automation activation The user must avoid any attempt to carry out work or repair on the automation system and always request the assistance of qualified personnel Anything which is not expressly provided ...

Страница 3: ...rque value between 1 and 99 5 Closing torque cls torque 50 Set the motor closing torque value between 1 and 99 6 Brake Brake 0 Set the required brake value between 0 and 99 compatibly with the weight of the gate and the existing stresses 7 Zone zone 0 Set the zone number between a minimum value of 0 and a maximum value of 127 See paragraph 7 on Serial connection 6 2 Logic Menu logic TCA tca ON ON ...

Страница 4: ... panel allows several automation units to be connected in a centralised way by means of appropriate serial inputs and outputs This makes it possible to use one single command to open and close all the automation units connected Following the diagram in Fig 5 proceed to connecting all the LEO control panels exclusively using a telephone type line Should a telephone cable with more than one pair be ...

Страница 5: ...6m TCA value expressed in seconds default 40 40s min 1 1s max 180 180s Encoder Ð value expressed in default 80 min 1 max 99 Opening torque Ð value expressed in default 50 min 1 max 99 Closing torque Ð value expressed in default 50 min 0 max 99 Brake Ð value expressed in default 0 min 1 max 99 Zone Ð numerical value default 0 min 0 max 127 Simultaneously press the and keys Simultaneous pressure of ...

Страница 6: ...o r s t a n d i n g w i t h i n t h e automation operating range RADIO MENU ADD Allows you to add one key of a radio control device to the receiver memory after storage it displays a m e s s a g e s h o w i n g t h e r e c e i v e r n u m b e r i n t h e memory location from 01 to 64 NOTE When using transmitters with two or more channels the first push button which has been stored is associated to...

Страница 7: ... ANT SWC PED OPEN CLOSE TIMER COSTA II CH R 24 V PHOT SW0 10 11 12 13 JP3 ANT SHIELD 24 V 40W max 34 35 36 37 38 39 40 41 JP9 4 5 6 7 8 9 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 OK Enter 8888 236 194 100 LEO SD 8888 24V 3W max SCA TX1 RX1 RX2 TX2 Fig 5 10 11 12 13 6 3 AF 0 315 AT 2AT D811327_03 LEO LEO CONTROL UNITS CONTROL UNITS ...

Страница 8: ...x 250m UNIFLAT 8888 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 D811327_03 LEO LEO CONTROL UNITS CONTROL UNITS ...

Страница 9: ...4 35 36 37 38 39 40 41 10 11 12 13 5 AF 0 315 AT 2AT M2 SLAVE M1 MASTER FIG 6a FIG 6b LEO M1 MASTER 1 2 3 4 5 6 7 8 9 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 10 11 12 13 5 AF 0 315 AT 2AT LEO M2 SLAVE TCA OFF STOP SWO2 SWC2 CC2 NC PHOT NC NC NC NC NC NC D811327_03 LEO LEO CONTROL UNITS CONTROL UNITS ...

Отзывы: