5) PROGRAMMING

The control panel provided with a microprocessor is supplied with function
parameters preset by the manufacturer, suitable for standard installations.
The  predefined  parameters  can  be  altered  by  means  of  either  the
incorporated display programmer or UNIPRO.
In  the  case  where  programming  is  carried  out  by  means  of  UNIPRO,
carefully  read  the  instructions  relating  to  UNIPRO,  and  proceed  in  the
following way.
Connect the UNIPRO programmer to the control unit through the UNIFLAT
accessory  (See  fig.  5).  Enter  the 

CONTROL  UNITS

  menu,  and  the

PARAMETERS

 submenu, then scroll the display screenfuls using the up/

down arrows, and set the numerical values of the parameters listed below.
For the function logics, refer to the 

LOGIC

 submenu.

In the case where programming is carried out by means of the incorporated
programmer, refer to Fig. A and B and to the 

configuration

 paragraph.

6) CONFIGURATION

The display programmer is used to set all the 

LEO

 control panel functions.

The programmer is provided with three pushbuttons for menu scrolling and
function parameter configurations (Fig. 2):
+

menu scrolling/value increment key

-

menu scrolling/value reduction key

OK

Enter (confirm) key

The simultaneous pressure of the + and 

 keys is used to exit the active

menu and move to the preceding menu.
If  the  +  and 

  keys  are  pressed  simultaneously  at  the  main  menu  level

(parameters, logics, radio, language, autosetting, self-diagnosis), programming
is exited and the display is switched off (the OK message is displayed).
The modifications made are only set if the OK key is subsequently pressed.
When the OK key is pressed for the first time, the programming mode is
entered.
The following pieces of information appear on the display at first:
-

Display Software version

-

Control unit Software version

-

Number  of  total  manoeuvres  carried  out  (the  value  is  expressed  in
thousands, therefore the display constantly shows 0000 during the first
thousand manoeuvres)

-

Number of manoeuvres carried out since the latest maintenance operation
(the value is expressed in thousands, therefore the display constantly
shows 0000 during the first thousand manoeuvres)

-

Number of memorised radio control devices.

When the OK key is pressed during the initial presentation phase, the first
menu (parameters) can be accessed directly.
Here  follows  a  list  of  the  main  menus  and  the  respective  submenus
available.
The predefined parameter is shown between square brackets 

[ 0 ]

.

The writing appearing on the display is indicated between round brackets.
Refer to Figures A and B for the control unit configuration procedure.

6.1) Parameter Menu (

PARAM

)

1- Pedestrian opening (

Mt. ped

) [ 001.0 m ]

Set the numerical value of the pedestrian opening  from 10 cm (000.1)
to 6m (006.0).

2- Automatic Closing Time (TCA) (

tca

)  [ 40s ]

Set  the  numerical  value  of  the  automatic  closing  time  from  1  to  180
seconds.

3- Encoder  (

Encoder

) [ 80 ]

Set the encoder sensitivity value from 1 to 99. A higher value corresponds
to  greater  sensitivity,  whereas  a  lower  value  corresponds  to  lesser
sensitivity.

WARNING: Check that the impact force value measured at the
points established by the EN 12445 standard is lower than that
specified in the EN 12453 standard.

Incorrect sensitivity setting can cause injuries to persons or
animals, or damage to things.

4- Opening torque (

open torque

) [ 50% ]

Set the motor opening torque value between 1% and 99%.

5- Closing torque (

cls. torque

) [ 50% ]

Set the motor closing torque value between 1% and 99%.

6- Brake (

Brake

) [ 0% ]

Set the required brake value between 0 and 99%, compatibly with the
weight of the gate and the existing stresses.

7- Zone (

zone

) [ 0 ]

Set the zone number between a minimum value of 0 and a maximum
value of 127. See paragraph 7 on 

Serial connection

.

6.2) Logic Menu (

logic.

)

- TCA  ( 

tca

 ) [ ON ]

ON

Activates automatic closing

OFF Excludes automatic closing

- 3 Steps (

3 step

)  [ OFF ]

ON

Enables 3-step logic. A start impulse has the following effects:
door closed: ............................................................................ opens
on opening: ............................ stops and enters TCA (if configured)
door open: .............................................................................. closes
on closing: ....................................... stops and reverses movement
after stopping: ......................................................................... opens

OFF Disables 3-step logic

- Opening Impulse lock (

Ibl open

) [ OFF ]

ON

The Start impulse has no effect during the opening phase.

OFF The Start impulse becomes effective during the opening phase.

- Impulse lock TCA (

ibl TCA

 ) [ OFF ]

ON

The Start impulse has no effect during the TCA dwell period.

OFF The Start impulse becomes effective during the TCA dwell period.

- Pre alarm (

pre-alarM

) [ OFF ]

ON

The blinker comes on about 3 seconds before the motor starts.

OFF The blinker comes on at the same time as the motor starts.

- Hold-to-run (

hold-to-run

 ) [ OFF ]

ON

Hold-to-run operation: the manoeuvre continues as long as the
command key is kept pressed.

OFF Impulse operation: one impulse opens the gate if closed, and closes

it if open.

- Rapid closing (

fast cls

 ) [ OFF ]

ON

Closes the gate after photocell disengagement, before waiting for
the end of the TCA (automatic closing time) set.

OFF Command not entered.

- Photocells on opening (

photc. open

) [ OFF ]

ON:

In case of obscuring, this excludes photocell operation on opening.
During the closing phase, it immediately reverses the motion.

OFF: In case of obscuring, the photocells are active both on opening and

on closing. When a photocell is obscured on closing, it reverses the
motion only after the photocell is disengaged.

- Master/Slave  (

Master

) [ OFF ]

ON

The control panel is set as Master in a centralised connection (see
Paragraph 7).

OFF The control panel is set as Slave in a centralised connection (see

Paragraph 7).

- Loop  (

loop

) [ OFF ]

ON

In the case of a closed loop centralised connection (Fig.5), set the
control unit to ON.

OFF In the case of an open centralised connection (Fig.5), set the control

unit to OFF.

6.3) Radio Menu (

radio

)

-

Add (

add

)

Allows you to add one key of a radio control device to the receiver memory;
after storage it displays a message showing the transmitter number in the
memory location (from 01 to 64).

NOTE:

When using transmitters with two or more channels, the first push-

button which has been stored is associated to the START function. If a
second  push-button  is  stored,  it  will  be  associated  to  the  pedestrian
function.

-

Read  (

read

)

Checks one key of a receiver; if stored it displays a message showing the
receiver number in the memory location (from 01 to 64), and the key number
(T1, T2, T3 or T4).

-

Delete  (

erase 1

)

Removes one single key of a transmitter from the receiver memory; after
deletion it displays a message showing the receiver number in the memory
location (from 01 to 64).

-

Eliminate list  (

erase 64

)

WARNING!

Completely removes all memorised radio control devices from

the receiver memory.

6.4) Language Menu (

Language

)

Allows you to set the language on the display programmer.
5 languages are available:

-

ITALIAN (

TA

)

-

FRENCH (

FRA

)

-

GERMAN (

DEU

)

-

ENGLISH (

ENG

)

-

SPANISH (

ESP

)

6.5) DEFAULT MENU (

default

)

Restores the preset default values on the control unit.

D811327_03

LEO

LEO

CONTROL UNITS

CONTROL UNITS

Содержание LEO

Страница 1: ...LEO CONTROL UNIT FOR ICARO D80000 00 00 99 Vers 00 ...

Страница 2: ... case of emergency Do not allow persons or children to remain in the automation operation area Keep radio control or other control devices out of children s reach in order to avoid unintentional automation activation The user must avoid any attempt to carry out work or repair on the automation system and always request the assistance of qualified personnel Anything which is not expressly provided ...

Страница 3: ...rque value between 1 and 99 5 Closing torque cls torque 50 Set the motor closing torque value between 1 and 99 6 Brake Brake 0 Set the required brake value between 0 and 99 compatibly with the weight of the gate and the existing stresses 7 Zone zone 0 Set the zone number between a minimum value of 0 and a maximum value of 127 See paragraph 7 on Serial connection 6 2 Logic Menu logic TCA tca ON ON ...

Страница 4: ... panel allows several automation units to be connected in a centralised way by means of appropriate serial inputs and outputs This makes it possible to use one single command to open and close all the automation units connected Following the diagram in Fig 5 proceed to connecting all the LEO control panels exclusively using a telephone type line Should a telephone cable with more than one pair be ...

Страница 5: ...6m TCA value expressed in seconds default 40 40s min 1 1s max 180 180s Encoder Ð value expressed in default 80 min 1 max 99 Opening torque Ð value expressed in default 50 min 1 max 99 Closing torque Ð value expressed in default 50 min 0 max 99 Brake Ð value expressed in default 0 min 1 max 99 Zone Ð numerical value default 0 min 0 max 127 Simultaneously press the and keys Simultaneous pressure of ...

Страница 6: ...o r s t a n d i n g w i t h i n t h e automation operating range RADIO MENU ADD Allows you to add one key of a radio control device to the receiver memory after storage it displays a m e s s a g e s h o w i n g t h e r e c e i v e r n u m b e r i n t h e memory location from 01 to 64 NOTE When using transmitters with two or more channels the first push button which has been stored is associated to...

Страница 7: ... ANT SWC PED OPEN CLOSE TIMER COSTA II CH R 24 V PHOT SW0 10 11 12 13 JP3 ANT SHIELD 24 V 40W max 34 35 36 37 38 39 40 41 JP9 4 5 6 7 8 9 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 OK Enter 8888 236 194 100 LEO SD 8888 24V 3W max SCA TX1 RX1 RX2 TX2 Fig 5 10 11 12 13 6 3 AF 0 315 AT 2AT D811327_03 LEO LEO CONTROL UNITS CONTROL UNITS ...

Страница 8: ...x 250m UNIFLAT 8888 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 D811327_03 LEO LEO CONTROL UNITS CONTROL UNITS ...

Страница 9: ...4 35 36 37 38 39 40 41 10 11 12 13 5 AF 0 315 AT 2AT M2 SLAVE M1 MASTER FIG 6a FIG 6b LEO M1 MASTER 1 2 3 4 5 6 7 8 9 21 22 23 24 25 26 27 28 29 30 31 34 35 36 37 38 39 40 41 10 11 12 13 5 AF 0 315 AT 2AT LEO M2 SLAVE TCA OFF STOP SWO2 SWC2 CC2 NC PHOT NC NC NC NC NC NC D811327_03 LEO LEO CONTROL UNITS CONTROL UNITS ...

Отзывы: