LEO MV D - Ver. 03 - 

13

D811512_03

INSTALLATION MANUAL

ENGLISH

-    Radio transmitter programming  (

radio prog

) [ ON ]

ON:  This enables transmitter storage via radio:
 

1 – First press the hidden key (P1) and then the normal key (T1, T2, 
T3 or T4) of a transmitter already  memorised in standard mode by 
means of the radio menu.

 

2 – Within 10s press the hidden key (P1) and the normal key (T1, T2, 
T3 or T4) of a transmitter to be memorised.

 

The receiver exits the programming mode after 10s, other new trans-
mitters can be entered before the end of this time. 

 

This mode does not require access to the control panel.

OFF:  This disables transmitter storage via radio.
 

The transmitters can only be memorised using the appropriate Radio 
menu.

6.3) Radio Menu (

radio

 

-   Add start (

add start

)

  Associates the required key to Start command
-   Read  (

read

  Checks one key of a receiver; if stored it displays a message showing 

the receiver number in the memory location (from 01 to 64), and the key 
number (T1, T2, T3 or T4).

-   Eliminate list  (

erease 64

)

  WARNING! Completely removes all memorised radio control devices from 

the receiver memory. 

-  Receiver code reading (

RX code

)

  This displays the code entered in the receiver.

6.4) Language Menu (

Language

)

Allows you to set the language on the display programmer.
5 languages are available:
-   ITALIAN (

TA

-   FRENCH (

FRA

-   GERMAN (

DEU

)

-   ENGLISH (

ENG

-   SPANISH (

ESP

6.5) MENU DEFAULT (

DEFAULT

)

Restores the preset default values on the control unit. After restoring, a new 
autoset operation must be carried out. 

6.6) DIAGNOSTICS AND MONITORING
The display on the LEO MV D panel shows some useful information, both 
during normal operation and in the case of malfunctions.

Diagnostics:
In the case of malfunctions, the display shows a message indicating which 
device needs to be checked:
STRT  

= START input activation

STOP  

= STOP input activation

PHOT  

= PHOT input activation

FLT   

= FAULT input activation for checked photocells 

SWO 

= input activation OPENING LIMIT SWITCH

SWC 

= input activation CLOSING LIMIT SWITCH

OPEN 

= OPEN input activation

CLS 

= CLOSE input activation

BAR 

= input activation SAFETY EDGE

TIME 

= TIMER input activation

In the case where an obstacle is found, the LEO MV D panel stops the door 
and activates a reverse manoeuvre; at the same time the display shows the 
“BAR” message.

6.7) Statistics
Having  connected  the  universal  palmtop  programmer  to  the  control  unit, 
enter  the  CONTROL  UNIT  /  STATISTICS  menu  and  scroll  the  screenful 
showing the statistical parameters:
-  Board microprocessor software version.
-  Number of cycles carried out. If motors are replaced, count the number 

of manoeuvres carried out up to that time. 

-  Number of cycles carried out from the latest maintenance operation. 
 

It is automatically set to zero after each self-diagnosis or parameter writing. 

-  Date of latest maintenance operation. To be updated manually from the 

appropriate menu “Update maintenance date”.

-  Installation  description.  16  characters  can  be  entered  for  installation 

identification.

7) CONNECTION TO PARKY CAR-PARK MANAGEMENT SYSTEM
The board is provided with an output (terminal JP4) for controlling the barrier 
status, configured as follows (Fig.7):
contact closed between terminals 19 and 20 with barrier lowered
contact closed between terminals 18 and 20 with barrier raised.

8) SERIAL CONNECTION USING SCS1 BOARD (Fig.5) 
The LEO-MV-D control panel allows several automation units (SCS1) to be 
connected in a centralised way by means of appropriate serial inputs and 
outputs. This makes it possible to use one single command to open and 
close all the automation units connected.
Following the diagram in Fig.5, proceed to connecting all the LEO-MV-D 
control panels, exclusively using a telephone-type line. 
Should a telephone cable with more than one pair be needed, it is indispens-
able to use wires from the same pair.
The length of the telephone cable between one appliance and the next must 
not exceed 250 m.
At this point, each of the LEO-MV-D control panels must be appropriately 
configured, by setting a MASTER unit first of all, which will have control over 
all the others, to be necessarily set as SLAVE (see logic menu).
Also set the Zone number (see parameter menu) between 0 and 127. 
The zone number allows you to create groups of automation units, each one 
answering to the Zone Master unit. Each zone can only be assigned one 
Master unit, the Master unit in zone 0 also controls the Slave units in 
the other zones.

8.1) Opposite barriers/gates (Fig.6)
Only with 3.7 or later microprocessor version.
By  means  of  a  serial  connection,  it  is  also  possible  to  obtain  centralised 
control of two opposite barriers/gates.
In this case, the Master M1 control panel will simultaneously manage closing 
and opening for the Slave M2 control panel.
SETTING REQUIRED FOR OPERATION:
-  MASTER board: 

zone

=128, 

master

=ON

-  SLAVE board: 

zone

=128, 

master

=OFF

WIRING REQUIRED FOR OPERATION:
-  The MASTER and SLAVE control units are interconnected through the 4 

wires (RX/TX) for the SCS1 interface boards;

-  All the activation controls, as well as the remote controls must refer to the 

MASTER board;

-  All the photocells (checked or unchecked) must be connected to the MAS-

TER control panel;

-  The safety edges (checked or unchecked) of the MASTER leaf must be 

connected to the MASTER control unit;

-  The safety edges (checked or unchecked) of the SLAVE leaf must be con-

nected to the SLAVE control unit.

9) SCRAPPING
Materials must be disposed of in conformity with the current regulations. 
In case of scrapping, the automation devices do not entail any particular 
risks or danger. In case of recovered materials, these should be sorted out 
by type (electrical components, copper, aluminium, plastic etc.).

10) DISMANTLING
WARNING:  before  opening  the  door,  make  sure  that  the  spring  has 
been unloaded (rod at 43°).
 When the automation system is disassembled 
to be reassembled on another site, proceed as follows:
-   Disconnect the power supply and the entire electrical installation.
-   Remove the actuator from its fixing base.
-   Disassemble all the installation components.
-   In the case where some of the components cannot be removed or are 

damaged, they must be replaced.

WARNINGS
Correct controller operation is only ensured when the data contained in 
the present manual are observed. The company is not to be held respon-
sible for any damage resulting from failure to observe the installation 
standards
 and the instructions contained in the present manual.

The descriptions and illustrations contained in the present manual are 
not binding. The Company reserves the right to make any alterations 
deemed appropriate for the technical, manufacturing and commercial 
improvement of the product, while leaving the essential product fea-
tures unchanged, at any time and without undertaking to update the 
present publication.

Содержание LEO MV D

Страница 1: ...CCIONES DE USO Y DE INSTALACION INSTRUÇÕES DE USO E DE INSTALAÇÃO I GB F D E P QUADRO COMANDO CONTROL PANEL CENTRALE DE COMMANDE STEUERUNG CUADRO DE MANDOS QUADRO DE COMANDO Via Lago di Vico 44 36015 Schio VI Tel naz 0445 696511 Tel int 39 0445 696533 Fax 0445 696522 Internet www bft it E mail sales bft it LEO MV D D811512 ver 03 21 05 07 8 027908 297235 ...

Страница 2: ... LEO MV D Ver 03 D811512_03 ...

Страница 3: ...e momento le modifiche che essa ritiene convenienti per migliorare tecnicamente costruttivamente e commercialmente il prodotto senza impegnarsi ad aggiornare la presente pubblicazione Thank you for buying this product our company is sure that you will be more than satisfied with the product s performance The product is supplied with a Warnings leaflet and an Instruction booklet These should both b...

Страница 4: ...ns or children to remain in the automation operation area Keep radio control or other control devices out of children s reach in order to avoid unintentional automation activation Theusermustavoidanyattempttocarryoutworkorrepairontheautoma tion system and always request the assistance of qualified personnel Anything which is not expressly provided for in the present instructions is not allowed Ins...

Страница 5: ...rque slud torque 99 Set the motor torque value during the slow down phase between 0 and 99 6 Opening torque open torque 70 Set the motor opening torque value between 1 and 99 7 Closing torque cls torque 70 Set the motor closing torque value between 1 and 99 8 Brake Brake 52 Set the required brake value between 0 and 99 compatibly with the weight of the rod and the existing stresses 9 Encoder Encod...

Страница 6: ...1 BOARD Fig 5 The LEO MV D control panel allows several automation units SCS1 to be connected in a centralised way by means of appropriate serial inputs and outputs This makes it possible to use one single command to open and close all the automation units connected Following the diagram in Fig 5 proceed to connecting all the LEO MV D control panels exclusively using a telephone type line Should a...

Страница 7: ...14 LEO MV D Ver 03 D811512_03 ...

Страница 8: ...LEO MV D Ver 03 15 D811512_03 ...

Страница 9: ...36 LEO MV D Ver 03 D811512_03 Fig 1 Fig 2 Fig 3 236 194 100 MOOVI BGV ...

Страница 10: ...s Contacts Kontakte Contactos Contatos 1 3 4 2 1 3 4 2 1 2 3 4 1 2 3 4 UNIPOWER UNIFLAT UNIFLAT UNIMITTO UNITRC UNIMITTO UNITRC P1 T1 Led T2 TRC 1 2 P1 P1 T1 T2 T3 T4 P1 P1 T1 Led T2 P1 P1 T1 T2 T3 T4 P1 P1 P1 Contatti Contacts Contacts Kontakte Contactos Contatos Programmatore palmare universale Universal palmtop programmer Programmateur de poche universel Universellen Palmtop Programmierer Progr...

Страница 11: ...38 LEO MV D Ver 03 D811512_03 Fig 6 Fig 5 SCS1 SCS1 SCS1 Max 250m TX1 TX2 RX1 RX2 TX1 TX2 RX1 RX2 TX1 TX2 RX1 RX2 SCS1 ...

Страница 12: ...LEO MV D Ver 03 39 D811512_03 Fig 7 JP4 18 19 20 NO NC COM JP4 18 19 20 NO NC COM ...

Страница 13: ......

Отзывы: