Control unit
m
3. TECHNICAL SPECIFICATIONS
- Power supply:
- Motor output:
- Flashing light/traffic light:
- Accessory output:
-Operating ambient temperature
4. INSTALLATION SAFETY
-10%, 50/60Hz -Operating ambient humidity
230Vac; 13A max
230Vac; 40W max
-Protection degree
24Vac; 1 A max
-Storage ambient temperature
-25
°
+60
°
C
3.1 CONTROL PANEL DIMENSIONS
..,
�
I
In order to reach the level of safety required by current regulations, read the following prescriptions carefully.
up to 95%
non condensing
IP55
-25
°
+60
°
C
1) Make all connections in the terminal block after carefully reading the instructions given in this manual and observing the general
rules and technical standards governing electrical systems.
2) Upstream from the installation, fit an omnipole miniature circuit breaker with a contact gap of at least 3 mm.
3) If there isn't one already, install a residual current device with a threshold of 30 mA.
4) Check the effectiveness of the grounding system and connect to it all the parts of the automation fitted with a terminal or grounding
cable.
5) Fit at least one external warning device, such as a traffic light or flashing light, along with a warning or danger sign.
6) Fit all the safety devices required by the type of installation, taking into consideration the risks it can cause.
7) Separate the power lines (min. sect. 1.5 mm
2
)
from the low-voltage signal lines (min. sect. 0.5 mm
2
)
in the ducts.
8
5. PRELIMINARY OPERATION
- Before sending a command to the automation, make sure to have selected correctly the type of bollard as follows:
Bollard selection
- Hold down buttons F and + for 5 seconds to select the connected bollard.
- Select the type of bollard using the b/-.
- Press F and + to confirm.
BOLLARD TABLE
[,6
PILLAR B 275/600
ES
EASY 0115-500 - STOPPY B 115/500
oS
STOPPY 0210-500
GB
PILLAR B 275/800 - XPASS B 275/800C
El
EASY 0200-700 - STOPPY B 200/700
ol
STOPPY 0210-700
H6
PILLAR B 275/600.6C SD
Fl
NOT AVAILABLE
us
NOT AVAILABLE
HB
PILLAR B 275/800.6C SD - XPASS B 275/800C SD
I l
NOT AVAILABLE
Ul
NOT AVAILABLE
H2
XPASS B 1200C
[R
NOT AVAILABLE
[,2
NOT AVAILABLE
dS
STOPPY MBB 219-500.C
[b
NOT AVAILABLE
dl
STOPPY MBB 219-700.C
- Select network frequency through Ht parameter. (see 3rd level programming).
-
(Hydraulic bollards only) Select the pressure switch type with the parameter
PP (see 3rd level programming).
- Check the connection method for simultaneous operation, if controlling multiple deterrent devices simultaneously (see paragraph 10).
6. INPUT AND OUTPUT FUNCTIONALITY AND CONNECTIONS
LINE
230V
6.1
m
POWER TERMINAL BLOCK
230V 50/60Hz power supply with varistor internal protection and SA T (5x20) plus 16A T (6.3x32) fuses.
Connect the phase and neutral as shown on the screen printing. Use a cable type H07RN-F 2x1 .5+E min.
Connect the yellow/green wire of the power supply mains to the earth terminal of the appliance.
- 25 -