INSTALLATION REQUIREMENTS
1.1
CONDITIONS OF INSTALLATION
It is the law that all gas appliances are installed only by a registered Installer, in
accordance with these installation instructions and the Gas Safety (Installation and
Use) Regulations 1998 as amended. Failure to install appliances correctly could
lead to prosecution. It is in your own interest and that of safety to comply with the
law.
The installation must also be in accordance with all relevant parts of the Local and
National Building Regulations where appropriate, the Building Regulations
(Scotland Consolidation) issued by the Scottish Development Department, and all
applicable requirements of the following British Standard Code of Practice.
1. B.S. 5871 Part 3 Installation of Decorative Fuel Effect Gas Fires
2. B.S. 6891 Installation of Gas Pipework
3. B.S. 5440 Parts 1 & 2 Installation of Flues and Ventilation
4. B.S. 1251 Open fire place components
5. BS 715 / BS EN 1856-2 Metal flue pipes for gas appliances
6. B.S. 6461 Part 1 Installation of Chimneys and flues
7. I.S. 813 : 1996 Domestic Gas Installation (Republic of Ireland)
No purpose made additional ventilation is normally required for this
appliance, when installed in G.B. When Installing in I.E. please consult
document I.S. 813 : 1996 Domestic Gas Installation, which is issued by the
National Standards Authority of Ireland. If installing in Northern Ireland,
please consult local building regulations. Any purpose made ventilation
must be checked periodically to ensure that it is free from obstruction.
1.2
FLUE AND CHIMNEY SUITABILITY
This appliance is designed for use with conventional brick built or lined chimneys
and fabricated flues and metal flue boxes conforming to BS 715 / BS EN 1856-2.
All flues must conform to the following minimum dimensions.
Minimum diameter of circular flues
125mm
Minimum length of 125mm flue types
4 metres
Minimum length of 175mm flue types
3 metres
Minimum length of 225mm x 225mm flue types 3 metres
IMPORTANT NOTE : Safe clearance of products must always be checked by
carrying out a smoke match test as described when installing into any of the
above stated flue types.
4