![Bewator Bewacard BC610 Скачать руководство пользователя страница 7](http://html1.mh-extra.com/html/bewator/bewacard-bc610/bewacard-bc610_installation-and-user-manual_2745188007.webp)
BC610 Installation and User manual
7
How to select connecting cables
It is important to use cables with the correct conductor gauge,
to keep the voltage drop in the cables as low as possible.
•
12 volt supplies
. A 12 V electric locking device generally
needs at least 11 V to work properly, so the voltage at the
card reader should never be less than 11 V.
•
24 volt supplies
. A 24 V electric locking device generally
needs at least 21 V to work properly, so the voltage at the
card reader should never be less than 21 V.
The recommended gauge (cross-sectional area) of the
conductor depends on the distance between the power supply
and the card reader, and on the load at the card reader.
The table below is for a Bewacard 610 with an electric
release. The total load is 300 mA at 24 V or 600 mA at 12 V.
24 V Supply
12 V Supply
Cable
length
(metres)
Min conductor
Min conductor
area
(mm
2
)
dia
(mm)
area
(mm
2
)
dia
(mm)
0-50
0.17
0.46
0.51
0.80
51-100
0.34
0.65
1.02
1.14
101-150
0.51
0.80
1.53
1.40
151-200
0.68
0.93
2.04
1.61
201-250
0.85
1.04
2.55
1.80
251-300
1.02
1.14
3.06
1.95