FENIX4 Monitoring system – Commissioning instruction
Management and service
The FENIX system is designed to facilitate management and service by present-
ing troubleshooting suggestions and measures for each specific service issue.
This means that you do not have to keep any troubleshooting manuals and other
documentation.
The unit will alert when the internal battery needs to be replaced. This can also be
done in connection with service or an obligatory ventilation control (OVK).
Instructions for replacing the battery
1. Power down the unit, no 230 V AC must be connected when replacing the
battery.
2. Remove the cover by loosening the screws as shown below.
3. Replace the CR2032 battery on the right side of the PCB.
Replace the battery within 10 seconds to prevent the unit from losing
its settings. If the unit is left without a battery connected for more than
10 seconds, any settings must be made again.
4. Refit the front by screwing on the cover again.
5. The unit automatically restarts with retained settings.