4
BORÅS
Tel +46 (0)33 - 23 67 80
STOCKHOLM
Tel +46 (0)8 - 54 55 12 70
FENIX4 Monitoring system – Commissioning instruction
2. Connection
Connect dampers, smoke detectors and other connections according to the
following connection instructions when the unit is powered down.
NOTE! If a smoke detector is not connected, then no
terminating resistance
should
be fitted.
The connection instructions for the ON/OFF damper (open/closed) are different
from the regulating 0-10 V damper, see the connection instructions.
4
6 7 8 9 10
DET1
DAMPER/
DAMPER 3
DAMPER/
DAMPER 4
5
32
FUNC.
TEST
33 34
EXT.
ALARM
35 36
NIGHT
MODE
37
S2
S6
G0
G
0-10
V
11
13 14 15 16 17
DET2
12
S2
S6
G0
G
0-10
V
18
20 21 22 23 24
DET3
19
S2
S6
G0
G
0-10
V
25
27 28 29 30 31
DET4
INPUTS
38
SUM.
ALARM
DET. SERV.
ALARM
39 40 41 42
44 45
EXT.
STOP
N
N
A
A
B
B
43
OUTPUTS
26
S2
S6
G0
G
C
46 47 48
NC
NO
C
C
NC
NO
NO
0-10
V
X
ON/OFF damper *)
X
2
6 4 1
5
1 2
3
5
X
3
5
2
1
1
4
6
2
3
FENIX 0-10 V
0-10 V damper *)
Example 0-10 V damper with
local control signal 1-10 V and
FENIX 0-10 V module
Example common
ON/OFF damper
X
X
0-10 V damper *)
X
2
6 4 1
5
5
1 2
3
3
Example 0-10 V damper
with control via
Modbus/BACnet
FENIX+
slave unit
X
X
DAMPER/
DAMPER 1
DAMPER/
DAMPER 2
1
2
3
230 VAC
100 VA
50 Hz
3
6
1
***) For
channel
detector
RCKD
**) At room
detector
RCRD
COM
FENIX4
FENIX+ slavenhet
Cable recommendations
ON/OFF dampers, e.g. BSKC6 = EKKR/ELQRB/EQQRB 4x1 mm
2
Regulating damper 0-10 V, e.g. BSKC6R = EKKR/ELQRB/EQQRB 5x1 mm
2
(7x1 mm
2
)
Between FENIX4 and FENIX+ slave units: UTP cable AWG22, AWG24 with 2 pairs.
A, , B, N must be connected (one conductor will be over).
Recommended max. length between FENIX4 master and FENIX+ slave unit: 300 m.
For local 0-10 V
control from, for
example room
sensors, the FENIX
0-10 V module
is used.
S2 S6 G0 G
X
X
FENIX4/FENIX+
0-10 V
S2 S6 G0
G0
G
0-10 V 0-10 V
S6
S2
S4
1
-
S1
0-10 V
2
+
FENIX 0-10 V
3 5
X
External 0-10 V signal
from room sensors,
for example
0-10 V damper *)
***) For duct detector RCKD
connected in series
**) For room detector RCRD
connected in series
*) 24 V DC max. 10 VA
When separate thermal
sensor is used, connect
in series with motor.
Thermal
sensor
Actuator
3
6
1
3
6
1
***) For duct detector RCKD
connected in series
**) For room detector RCRD
connected in series
*) 24 V DC max. 10 VA
When separate thermal
sensor is used, connect
in series with motor.
Thermal
sensor
Actuator
3
6
1
3
6
1
***) For duct detector RCKD
connected in series
**) For room detector RCRD
connected in series
*) 24 V DC max. 10 VA
When separate thermal
sensor is used, connect
in series with motor.
Thermal
sensor
Actuator
3
6
1
3
6
1
N A B
46 47 48
EFX communication line
Screen & ”N” connection optional
4
6 7 8 9 10
DET1
DAMPER/
DAMPER 3
DAMPER/
DAMPER 4
5
S2
S6
G0
G
0-10
V
11
13 14 15 16 17
DET2
12
S2
S6
G0
G
0-10
V
18
20 21 22 23 24
DET3
19
S2
S6
G0
G
0-10
V
25
27 28 29 30 31
DET4
N
N
A
A
B
B
26
S2
S6
G0
G
46 47 48
0-10
V
X
ON/OFF damper *)
X
2
6 4 1
5
1 2
3
5
X
3
5
2
1
1
4
6
2
3
FENIX 0-10 V
0-10 V damper *)
Example 0-10 V
Example ON/OFF
Connections
in RCHD
Connections
in RCHD
Connections in
RCHD
Connections in
RCKD
X
X
DAMPER/
DAMPER 1
DAMPER/
DAMPER 2
1
2
3
SLAVE ADDRESS
3
1
2
230 VAC 100 VA 50 Hz
1 2
Overtemperature detector RCHD
together with smoke detector
1 2
1
2
1 2 3 4 5
FENIX+
slave unit
FENIX+ slave unit
or FENIX4
COM
4
6 7 8 9 10
DET1
DAMPER/
DAMPER 3
DAMPER/
DAMPER 4
5
S2
S6
G0
G
0-10
V
11
13 14 15 16 17
DET2
12
S2
S6
G0
G
0-10
V
18
20 21 22 23 24
DET3
19
S2
S6
G0
G
0-10
V
25
27 28 29 30 31
DET4
N
N
A
A
B
B
26
S2
S6
G0
G
46 47 48
0-10
V
X
ON/OFF damper *)
X
2
6 4 1
5
1 2
3
5
X
3
5
2
1
1
4
6
2
3
FENIX 0-10 V
0-10 V damper *)
Example 0-10 V
Example ON/OFF
Connections
in RCHD
Connections
in RCHD
Connections in
RCHD
Connections in
RCKD
X
X
DAMPER/
DAMPER 1
DAMPER/
DAMPER 2
1
2
3
SLAVE ADDRESS
3
1
2
230 VAC 100 VA 50 Hz
1 2
Overtemperature detector RCHD
together with smoke detector
1 2
1
2
1 2 3 4 5
FENIX+
slave unit
FENIX+ slave unit
or FENIX4
COM