background image

5

BORÅS

 

Tel +46 (0)33 - 23 67 80      

STOCKHOLM

 

Tel +46 (0)8 - 54 55 12 70

FENIX4 Monitoring system – Commissioning instruction

For local 0-10 V  
control from, for  
example room  
sensors, the FENIX  
0-10 V module  
is used.

Connection terminals Function

Description

4+5, 11+12, 18+19, 
25+26

Connection of smoke detector 
circuits

Each smoke detector circuit should have a 2.2 kOhm's resistance mounted at the 
end of the circuit, see the wiring diagram. The terminating resistance of 2.2 kOhm is 
connected to the last detector in each circuit. If a central fire alarm and/or no smoke 
detectors are used, a resistance of 2.2 kOhm should not be installed on these terminals. 
Max 24 V DC 90 mA.

6-10, 13-17, 20-24, 
27-31

Connection of fire damper

For standard ON/OFF dampers, the input is not used for 10 V, this is done only for regu-
lating dampers, see wiring diagrams. 
The damper output on G and G0 is 24 V DC, max 10 VA per output.

Note! Only 1 fire damper per output!

Inputs

Function

Description

32+33

External function test/resetting 
External alarm

In the event of a short circuit, the controller performs a functional test and may reset the 
external incoming alarm, provided that terminals 34+35 do not have an open circuit. 
These terminals cannot be jumpered for automatic resetting. Instead, see options under 
settings.

34+35

External incoming alarm

In the event of an open circuit between terminals, External incoming alarm is activated, 
jumpered on delivery and if External incoming alarm is not used.

36+37

Night mode

In the event of short circuiting of the terminals, the panel enters Night mode whereby 
all dampers close without the controller generating alarms. Used, for example, during 
intermittent operation. Night mode can also be a good safety measure for preventing the 
spread of combustion gases when the ventilation is switched off, duct-mounted smoke 
detectors do not have the same opportunity to detect smoke when no air is transported 
in the system. 

Outputs

Function

Description

38+39+40

Main alarm

Potential-free changeover contact that switches for: 
• Detector failure • Damper failure • Tripped detector • External incoming alarm  
• Power outage • System failure • Communication failure with slave units  
• Internal battery needs to be replaced 
In normal operation, terminals 38+40 have contact. 
Drawn in de-energised/alarm mode. 
Max 24 V AC/DC, 3 A

41+42+43

Service alarm detector circuits

Potential-free changeover contact that switches for soiled detector. 
In normal operation, terminals 41+43 have contact.
Drawn in de-energised/alarm mode. 
Max 24 V AC/DC, 3 A

44+45

External stop of fan/ 
unit

Breaking potential-free contact that breaks for: 
• Functional testing of fire dampers • Main alarm 
In normal operation, terminals 44+45 have contact. 
Drawn in de-energised/alarm mode. 
Max 24 V AC/DC, 3 A

46+47+48

Bus contact, communication 
between FENIX and FENIX+

Communication cable between FENIX and FENIX+ is connected here.

44+45

External stop of fan/ 
unit

Breaking potential-free contact that breaks for: 
• Functional testing of fire dampers • Main alarm 
In normal operation, terminals 44+45 have contact. 
Max 24 V AC/DC, 3 A

Network connection

Cable connection RJ45, 10Base-T/100Base-TX auto-negotiation
Cable length Max. 100 m
Cabling Min. Cat 5

SLAVE

ADDRESS

3

1

2

Addressing slave units

Addressing knob for slave unit (FENIX+ only). Connected slave units shall be addressed 
in the order: 1, 2, 3. Turn the knob to change the address.

 

Indication of communication 
between master unit FENIX 
and slave unit FENIX+

Green LED on
Red LED on
Orange flashing 1 time/sec

Voltage on, everything OK                       
Battery problems FENIX4
No contact between FENIX+ and FENIX4

2. Connection cont.

•  Measure the voltage with a 

multimeter use a well-known 
brand.

•  Check cables using an 

Ohmmeter with all devices 
disconnected.

•  Never use a megohmmeter!

•  The connection and discon-

nection of all cables are made 
with FENIX4 master and 
FENIX+ slave unit powered 
down.

Содержание FENIX+

Страница 1: ...www bevent rasch com FIRE SAFETY 22 01 2021 FENIX4 FENIX Monitoring system Commissioning instruction ...

Страница 2: ...ay be damaged in the event of improper use When connecting dampers smoke detectors and other connections the unit must be powered down The cover to access the terminal blocks is removed by unscrewing the cover on the lower part of the control unit The connection terminals for 230 V AC are opened by inserting a screwdriver with a suitable width into the notch above the connector and then bend the s...

Страница 3: ...regulation can be performed in two different ways either via a local 0 10 V signal out at the damper or via master communication Modbus TCP or BACnet IP If local control is desired with 0 10 V the FENIX 0 10 V module is used to separate the local control signal from e g a room sensor and the 10 V signal from FENIX that takes over during a functional test to check that the dampers can open 20 Nov 0...

Страница 4: ...0 10 V 3 5 X External 0 10 V signal from room sensors for example 0 10 V damper For duct detector RCKD connected in series For room detector RCRD connected in series 24 V DC max 10 VA When separate thermal sensor is used connect in series with motor Thermal sensor Actuator 3 6 1 3 6 1 For duct detector RCKD connected in series For room detector RCRD connected in series 24 V DC max 10 VA When separ...

Страница 5: ... detect smoke when no air is transported in the system Outputs Function Description 38 39 40 Main alarm Potential free changeover contact that switches for Detector failure Damper failure Tripped detector External incoming alarm Power outage System failure Communication failure with slave units Internal battery needs to be replaced In normal operation terminals 38 40 have contact Drawn in de energ...

Страница 6: ...nhet N A B 46 47 48 EFX communication line Screen N connection optional 4 6 7 8 9 10 DET1 DAMPER DAMPER 3 DAMPER DAMPER 4 5 S2 S6 G0 G 0 10 V 11 13 14 15 16 17 DET2 12 S2 S6 G0 G 0 10 V 18 20 21 22 23 24 DET3 19 S2 S6 G0 G 0 10 V 25 27 28 29 30 31 DET4 N N A A B B 26 S2 S6 G0 G 46 47 48 0 10 V X ON OFF damper X 2 6 4 1 5 1 2 3 5 X 3 5 2 1 1 4 6 2 3 FENIX 0 10 V 0 10 V damper Example 0 10 V Example...

Страница 7: ...tem cannot be start ed Use the troubleshooting guide on the display to correct the fault before commissioning Check that the number of fire dampers and smoke detector circuits found match the installation Use the troubleshooting guide on the display if your dampers or smoke detector circuits are not displayed NB The icons also show whether the dampers are of ON OFF type or regulating 0 10 V Exampl...

Страница 8: ...CUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 DAMPER 1 DAMPER 1 AMPER AMPER SLAVE 1 DAMPER 1 AMPER AMPER CIRCUIT 1 CIRCUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 DAMPER 1 DAMPER 1 AMPER AMPER SLAVE 1 DAMPER 1 AMPER AMPER CIRCUIT 1 CIRCUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 DAMPER 1 DAMPER 1 AMPER AMPER SLAVE 1 DAMPER 1 AMPER AMPER CIRCUIT 1 CIRCUIT 1 RCUI IRCUIT RCUIT C CIRCUIT 1 SLAVE 1 CIRC...

Страница 9: ...ers is performed first after a 5 minute delay which then allows the electric heating coils to cool down Default setting no delay Automatic reset of External incoming alarm Normally an External incoming alarm 34 35 needs to be acknowledged on the unit via the display or terminal block 32 33 default setting this function permits External incoming alarms to be acknowledged automatically when a possib...

Страница 10: ...so be done in connection with service or an obligatory ventilation control OVK Instructions for replacing the battery 1 Power down the unit no 230 V AC must be connected when replacing the battery 2 Remove the cover by loosening the screws as shown below 3 Replace the CR2032 battery on the right side of the PCB Replace the battery within 10 seconds to prevent the unit from losing its settings If t...

Страница 11: ...11 BORÅS Tel 46 0 33 23 67 80 STOCKHOLM Tel 46 0 8 54 55 12 70 FENIX4 Monitoring system Commissioning instruction ...

Страница 12: ...190703 0002_ENG January 2021 teamfront se www bevent rasch com ...

Отзывы: