BEST POWER 610 - UPS Installation
Model Shown:
0610-3000U soft-wired version
Your UPS is fitted with a DB9 communications
connector on the rear panel. From this connector,
you can access opto-coupled outputs indicating
mains failure or low battery. The contact ratings
are 30 VDC at 10 mA. The diagram below shows
DB9 contact connections.
Alternatively, RS232 serial communication is
available. This RS232 provides a proprietary
command sequence for the computer to monitor the
utility and the UPS status and to control the UPS
output. The data format of the RS232 is 2400 bps, 8 bit
data, 1 stop bit and no parity.
The battery test mode is also available through the
RS232 command sequence when the UPS is operating
and the power is normal. During the test, the 4 LED’s
(line, bypass, battery and inverter) will light alternatively
until the test is completed.
Each UPS is supplied with a package of CHECKUPS
II® Advanced UPS communications software.
This package includes the correct interconnection
cable for your Best Power 610 UPS. If your computer
does not have a DB9 connector on the serial port, use
a standard DB9-DB25 adaptor, available at most
computer accessory stores. The CD-ROM provided with
your UPS includes software for many standard
operating systems. Refer to section 4.1 for more
details of CheckUPS II® and its capabilities.
If you are adding the optional Best Relay Card
(AS400®), refer to Section 5.2 for instructions to install
the card. Be careful to connect your Best Relay
(AS400®) interface cable to the correct DB9 connector.
Refer to Section 5.2 for more details of the Best Relay
(AS400®) card option.
If you are adding the BestLink SNMP/Web option card,
refer to Section 5.3 for instructions to install the card.
Only one (1) card, either Best Relay (AS400®)
or
SNMP, can be fitted into the slot at any one time.
2.9 Setting up the UPS Monitoring from your Computer
5
Note 1: Remote shutdown is
available in battery mode only,
with no mains input power.
Keeping pin 6 at +5 to +12 VDC
for 1 second will turn off the UPS
inverter.
N. O.
Closes
on
Input
Mains
Failure
N. C.
Opens
on
Input
Mains
Failure
N. O.
Closes
on
Low
Battery
Rs232
transmit Data
Rs232
Receive Data
See Note 1.
Rs232 Ground
DB9